background image

 

Service & Support 

Answers for industry. 

 

 

 

Cover sheet

Operating System Update with 

 

WinCC (TIA Portal) 

WinCC (TIA Portal) 

FAQ 

 July 2012 

background image

Question 

 

 

 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

This entry is from the Service&Support portal of Siemens AG, Sector Industry, 
Industry Automation and Drive Technologies. The conditions of use specified there 
apply 

(

www.siemens.com/nutzungsbedingungen

)

 

Go to the following link to download this document. 

http://support.automation.siemens.com/WW/view/en/19701610

  

 

 

 

 

 

 

 

 

 

Question 

How do you do an operating system update (OS update) on operator panels  
with WinCC (TIA Portal)? 

 

 

 

Answer 

Follow the instructions and notes listed in this document for a detailed answer to 
the above question. 

 

 

 

 

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

 

Contents 

1

 

Operating System Update with  WinCC (TIA Portal) ...................................... 5

 

1.1

 

Operating System Update (OS Update)............................................... 6

 

1.2

 

Resetting the Operator Panel to the Factory Settings (Booting).......... 7

 

1.2.1

 

Operator Panel with Defective Operating System ............................... 7

 

1.2.2

 

Operator Panel with Intact Operating System...................................... 9

 

2

 

Additional Information .................................................................................... 11

 

2.1

 

Cable Connection between PC and Operator Panel ......................... 11

 

2.1.1

 

Operating System Update .................................................................. 11

 

2.1.2

 

Resetting the Operator Panel to the Factory Settings (Booting)........ 11

 

2.2

 

Set the Image Path / File in ProSave ................................................. 13

 

2.2.1

 

Image Path in WinCC (TIA Portal) ..................................................... 14

 

2.2.2

 

Image Path in WinCC flexible 2008 ................................................... 14

 

2.3

 

Determine the MAC Address ............................................................. 14

 

3

 

Problem Analysis............................................................................................. 15

 

3.1

 

Disconnection with the  RS232/PPI Multi--Master- Cable.................. 15

 

3.2

 

Check Box Not Available in ProSave ................................................. 15

 

3.3

 

Check Box Cannot be Deselected in ProSave .................................. 15

 

3.4

 

Error Message during the Transfer of the Configuration.................... 17

 

3.5

 

Comfort Panel "Reset to factory settings" .......................................... 17

 

3.6

 

MP 377 "Reset to Factory Settings" (Booting) ................................... 17

 

3.7

 

A Connection to the Operator Panel Cannot be Established............. 18

 

3.7.1

 

Check Transmission Type and Address on the Operator Panel........ 18

 

3.7.2

 

Check Cable Connection and Connector........................................... 19

 

3.7.3

 

Check the PG/PC Interface on the Configuration Computer ............. 20

 

 

 

 

 

 

background image
background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

 

Operating System Update with  
WinCC (TIA Portal) 

When you install WinCC (TIA Portal), an Image file is installed as well for each 
operator panel listed in the hardware catalog of WinCC (TIA Portal). On the

 

configuration PC, there is always only one Image file per operator panel. This 
depends on the version of WinCC (TIA Portal) installed.  
When you install a newer or older version of WinCC (TIA Portal), the Image files 
available are replaced by the currently installed version of WinCC (TIA Portal). 

The Image file includes the operating system and system files of the operator panel 
concerned. 

Note 

As from WinCC V11 you no longer need an operating system update in the 
different versions (for example, WinCC V11 SP1, WinCC V11 SP2, etc.). When 
you transfer a project, all the currently associated system files (DLLs) are also 
transferred automatically to the operator panel. The Basic Panels are the 
exception here. 

 

Below we provide you with an overview of when you must update an operating 
system and how to do the update with WinCC (TIA Portal).  
•  If the operating system of an operator panel is not compatible with the version 

of WinCC (TIA Portal) currently being used. 

•  If an Image file version of WinCC flexible is installed on the operator panel. 

In both cases mentioned above you must update the operating system on the 
operator panel before transferring the project. 
Information about this is available in section 1.1 "Operating System Update 
(OS Update)"

•  If there is no operating system running on the operator panel, then you can 

only update the operating system using the  
"Reset to factory settings" function.  
Information about this is available in section 1.2 "Resetting the Operator Panel 
to the Factory Settings (Booting)".  

•  If you have questions about establishing the connection or problems with the 

operating system update, please refer to chapters 2 "Additional Information" 
and 3 "Problem Analysis".  

 

Notes 

Updating the operating system deletes all the data on the operator panel. 

Therefore, first make a backup of the data below
(using ProSave or Automation License Manager, for example) 

•  User administration (ProSave) 
• Recipes 

(ProSave) 

• Licenses 

(Automation License Manager), if you reset the operating system to the 

factory settings. 
Information about this is available in Entry ID

27005215

  

 

 

 

background image

Contents 

 

 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

1.1 

Operating System Update (OS Update) 

Before making a project transfer WinCC (TIA Portal) checks the version  
of the operating system installed on the operator panel connected.  
If the operating system installed on the operator panel is different to the version of 
WinCC (TIA Portal) being used, you get the message below. (For example, if a 
WinCC flexible Image is installed on the operator panel or a Basic Panel is 
concerned.) 

Figure 1-1 

 

 

If you confirm with the "Yes" button, the version of the operating system on the 
operator panel is updated automatically and the configuration is transferred. 

 

Notes 

Before starting the operating system update, set the operator panel to Transfer 
mode.  

 

 

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

 

1.2 

Resetting the Operator Panel to the Factory Settings 
(Booting) 

If there is no operating system running on the operator panel, then you can only 
update the operating system using the "Reset to factory settings" function. This is 
the case, for example, if the following message is displayed when you start up the 
operator panel: No image found. Waiting for image update…,  

Another application is when you would like to reset all the settings in the Control 
Panel of the operator panel to the factory settings. In this case, too, you can use 
the "Reset to factory settings" function.   

 

Notes 

If you reset the operating system to the factory settings, you cannot use all the 
communication connections and cables.  

Information about which cable you can use for which operator panel is available 
in section 2.1.2 "Resetting the Operator Panel to the Factory Settings (Booting)". 

 

 

1.2.1 

Operator Panel with Defective Operating System  

Table 1-1 

No. 

Procedure 

1.  Back Up Licenses and Authorizations 

If the operator panel no longer boots automatically, then you can no longer access 
the file system. Then you cannot back up the existing recipes and licenses.   

2.  PG/PC: Setting the PG/PC interface  

You only have to make a setting in the PG/PC interface with the "Ethernet" transfer 
type.  
•  Open the "PG/PC interface" under  

"Start > Settings > Control panel > Set PG/PC interface".  

– 

Select S7ONLINE under "Access point of the application". 

– 

Under "Interface Parameter Assignment Used" you select  
"TCP/IP -> <Network Card Name>".  

3.  Operator panel: make transfer settings on the operator panel 

No transfer settings can or need to be made on the operator panel.  

4.  Operator panel: power supply  

Switch off the power supply for the operator panel. 

5.  Establish cable connection 

Connect the operator panel to the PG/PC according to the transfer type selected.   

background image

Contents 

 

 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

No. 

Procedure 

6.  WinCC (TIA Portal): set transfer mode  

You select the PG/PC interface depending on the communication connection 
selected - serial, USB/PPI or Ethernet.  
•  In the project navigation, mark the operator panel of which the  

Image file is to be updated.  

•  In the menu bar you select "Online > Extended download to device...". 
•  Make the relevant settings in the dialog displayed. 

– 

Ethernet: 
An Ethernet address does not have to be specified. You can apply a 
configured Ethernet address (Config IP).   

– 

Serial:  
You can specify a baud rate of your choice.  
Note: 
For project transfer with the RS232/PPI multi-master cable you must set 
the fifth DIP switch to the ZERO position (PPI/Freeport). Use the DIP 
switches to set the highest baud rate on the cable.  

•  Click the "Load" button.  

The "Load preview" window opens. 

• "Load 

preview" 

window. 

When the "Load preview" window opens, the configuration is compiled and the 
system applies the transfer settings made.  
Close the window with the "Cancel" button. 

 
Note: 
From now on you cannot change the transfer type. 

7.  WinCC (TIA Portal): reset to the factory settings 

•  In the "Online > HMI operator panel maintenance" menu bar you select the 

"Update operating system" command. 
The SIMATIC ProSave [OS Update]" dialog opens.  
The path with the image of the operating system is already preset.  
(You can also choose a different path for the image of the operating system). 

•  Enable the "Reset to factory settings" option.  

The input field is displayed for the MAC address with the "Ethernet" transfer 
type. In this case, you enter the operator panel's "MAC address".  
Refer to section 2.3 for how to determine the MAC address.  

•  Click the "Update OS" button.  

You will then receive a security warning.  
Read the note. Acknowledge the message with "Yes" and you will be requested 
to reboot the operator panel.  

•  Switch the operator panel on again. The Image file update starts. (This 

procedure start can take quite a long time).  

 
Note 
If the "Reset to factory settings" check box is not displayed, refer to section 3.2.   

8.  Transfer project 

After the installation has been completed, the operator panel remains in Transfer 
mode.  
For a subsequent project transfer, you first make the required transfer settings on 
the operator panel.  
For Touch operator panels, you should calibrate the screen beforehand under 
"Control Panel > OP > Touch".  

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

 

1.2.2 

Operator Panel with Intact Operating System  

Below we take the example of a TP700 Comfort to show how to reset an operator 
panel to the factory settings via Ethernet. 

Table 1-2 

No. 

Procedure 

1.  PG/PC: back up licenses, recipes, etc. 

Before resetting your operator panel to the factory settings, make sure that there are 
no licenses, recipes, etc. on the operator panel.  
The "Reset to factory settings" function deletes all the data on the operator panel.  
 
Therefore, first make a backup of the data below 
(using ProSave or Automation License Manager, for example). 
•  User administration (ProSave) 
• Recipes 

(ProSave) 

•  Licenses (Automation License Manager) 

More information about this is available in Entry ID: 

27005215

   

2.  PG/PC: set the PG/PC interface  

You only have to make a setting in the PG/PC interface with the  
"Ethernet" transfer type.  
•  Open the "PG/PC interface" under  

"Start > Settings > Control panel > Set PG/PC interface".  

– 

Select S7ONLINE under "Access point of the application". 

– 

Under "Interface Parameter Assignment Used" you select "TCP/IP -> 
<Network Card Name>
".  

3.  Operator panel: MAC address of the operator panel 

To continue you need the MAC address of the operator panel. 
Please refer to section 2.3 to determine the MAC address. 

4.  Operator panel: boot settings on the operator panel 

•  In the Control Panel of the operator panel you open the “OP" dialog and select 

the "Device" tab. 

•  Click the "Reboot" button. Another window opens with two "boot options".  

– 

Reboot  

– 

Prepare for Reset  

Leave this window open for the time being. 

5.  Establish cable connection 

Connect the operator panel and the PG/PC using an Ethernet cable  
(cross-over or patch cable).  

background image

Contents 

 

 

10 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

No. 

Procedure 

6.  WinCC (TIA Portal): set transfer mode  

If "Ethernet" is not preset for the transfer mode, then proceed as follows.  
•  In the project navigation, mark the operator panel of which the operating system 

is to be updated.  

•  In the menu bar you select "Online > Extended download to device...".  
•  Make the relevant settings in the dialog displayed. 

– 

PG/PC interface type:  Ethernet  

– 

PG/PC interface:   

 

Ethernet  

•  Click the "Load" button. 

 The "Load preview" window opens.  

• "Load 

preview" 

window. 

When the "Load preview" window opens, the configuration is compiled and the 
system applies the transfer settings made.  
Close the window with the "Cancel" button. 

 
Note: 
From now on you cannot change the transfer type.   

7.  Operator panel: reset to the factory settings 

•  In the "Online > HMI operator panel maintenance" menu bar you select the 

"Update operating system" command. 
The "SIMATIC ProSave [OS Update]" dialog opens.  
The path with the image of the operating system is already preset.  
(You can also choose a different path for the image file).  

•  Enable the "Reset to factory settings" option.  

An input field is displayed for the MAC address. 

•  Enter the operator panel's "MAC address".  

Refer to section 2.3 for how to determine the MAC address.  

•  Click the "Update OS" button.  

You will then receive a security warning.  
Read the note. Acknowledge the message with "Yes" and you will be requested 
to reboot the operator panel.  

•  On the operator panel you click the "Prepare for Reset"  

(

see link

). 

The operator panel boots automatically and is reset to the factory settings.  
(This procedure start can take quite a long time).  

 
Note 
If the "Reset to factory settings" check box is not displayed, refer to section 3.2.   

8.  Transfer project 

After the installation has been completed, the operator panel remains in Transfer 
mode.  
For a subsequent project transfer, you first make the required transfer settings on 
the operator panel.  
For Touch operator panels, you should calibrate the screen beforehand under 
"Control Panel > OP > Touch". 

 

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

11 

 

Additional Information 

2.1 

Cable Connection between PC and Operator Panel 

2.1.1 

Operating System Update 

When performing an operating system update, you can use all the communication 
connections supported by your operator panel. 

2.1.2 

Resetting the Operator Panel to the Factory Settings (Booting) 

If you reset the operating system to the factory settings, you cannot use all the 
communication connections and cables.  

Information on this is available in the table below.  
The settings were made in ProSave version V9.0.0.0.  

Table 2-1 

Operator Panel 

RS 232 

Zero modem 

cable 

RS232/PPI 

Multi-master 

cable 

USB/PPI 

Multi-master 

cable 

PN PtP 

Cross 

PN 

Ethernet 

 6ES7 

901-

1BF00-0XA0 

6ES7 901-
3CB30-0XA0 

6ES7 901-
3DB30-0XA0 

6XV1 870-

3RH20 

*

1

Standard 
Ethernet CAT5

KP300

 

Basic mono PN 

-- -- -- X 

X 

KTP400

 

Basic mono PN 

-- -- -- X 

X 

KTP600

 

Basic DP 

-- 

X 

X -- -- 

KTP600

 

Basic PN 

-- -- -- X 

X 

KTP600

 

Basic mono PN 

-- -- -- X 

X 

KTP1000

 

Basic DP 

-- 

X 

X -- -- 

KTP1000

 

Basic PN 

-- -- -- X 

X 

TP1500

 

Basic PN 

-- -- -- X 

X 

OP 73 

 

 

-- 

X 

X -- -- 

OP 77A

 

 

-- 

X 

X -- -- 

OP 77B

 

 

X -- -- -- -- 

TP 177A

 

 

-- 

X 

X -- -- 

TP 177B 

 

PN/DP 

-- 

X 

X

*2

-- -- 

TP 177B 

 

mono DP 

-- 

X 

X

*2

-- -- 

TP 177B 4"

 

color PN/DP 

-- -- -- X 

X 

OP 177B 
PN/DP 

-- 

X 

X

*2

-- -- 

background image

Contents 

 

 

12 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

Operator Panel 

RS 232 

Zero modem 

cable 

RS232/PPI 

Multi-master 

cable 

USB/PPI 

Multi-master 

cable 

PN PtP 

Cross 

PN 

Ethernet 

OP 177B 

 

mono DP 

-- 

X 

X

*2

-- -- 

TP 277 

 

 

-- 

X 

X

*2

-- -- 

OP 277

 

 

-- 

X 

X

*2

-- -- 

KP400 

 

Comfort 

-- -- -- X 

X 

KTP400 
Comfort 

-- -- -- X 

X 

KP700 

 

Comfort 

-- -- -- X 

X 

TP700 

 

Comfort 

-- -- -- X 

X 

KP900 

 

Comfort 

-- -- -- X 

X 

TP900 

 

Comfort 

-- -- -- X 

X 

KP1200 
Comfort 

-- -- -- X 

X 

TP1200 
Comfort 

-- -- -- X 

X 

MP177

 

 

-- 

X 

X

*2

-- -- 

MP 277

 

 

-- 

X 

X

*2

-- -- 

MP 377

 

 

-- -- -- X 

X 

Mobile Panel 
177 DP 

-- 

X 

X

*2

-- -- 

Mobile Panel 
177 PN 

-- 

X 

X

*2

-- -- 

Mobile Panel 
277 

-- 

X 

X

*2

-- -- 

 

 

*

1

) For the RS232/PPI multi-master cable you set DIP switches 1 to 3 according to 

the baud rate selected in ProSave.  
DIP switches 4 to 8 must all be set to ZERO. 

*2

With this cable connection you cannot deselect the "Reset to factory settings" 
option. 

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

13 

 

2.2 

Set the Image Path / File in ProSave 

In the following case, you must change the Image path or the Image file 
accordingly. 

After you have set the WinCC flexible Image path for the operator panel displayed, 
you must set the Image path for WinCC (TIA Portal) if you now wish to use the 
same operator panel in WinCC (TIA Portal). 

 

Notes 

•  The image path setting is device-related. The setting is retained for the selected 

panel type after ProSave is closed.  

• Beforehand, 

make 

sure that the correct Image path is set. This applies, in particular, 

if WinCC flexible and WinCC (TIA Portal) are installed jointly on your computer.  

 

 

In order to set the image path in ProSave, click the button to the right of the Image 
path and browse through the folder tree to specify the folder path in which the 
Image files are located.  

In the folders you find the image files required for the respective operator panel. 

Figure 2-1 

 

 

 

background image

Contents 

 

 

14 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

2.2.1 

Image Path in WinCC (TIA Portal) 

Sample Image path in WinCC (TIA Portal)   

C:\Program Files\Siemens\Automation\\Portal V11\Data\Hmi\Transfer\11.0\Images 
\OperatorPanel\*.img  

 

2.2.2 

Image Path in WinCC flexible 2008  

Sample Image path in WinCC flexible 2008   

C:\Program Files\Siemens\SIMATIC WinCC flexible\WinCC flexible 
Images\Operator Panel\*.img 

 

 

2.3 

Determine the MAC Address 

You can determine the operator panel's MAC address as follows. 
•  The MAC address is printed on the back of the operator panel  

(for example, MAC-ADD.: 00-0E-8C-F8-6A-18). 

•  When you switch on the operator panel, the MAC address is displayed during 

startup. 

•  By way of the "Control Panel" of the operator panel. 

In the Control Panel you open the "OP" dialog and select the "Device" tab. 
This tab contains the device-specific data like the MAC address. 

background image

Contents

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

15 

 

Problem Analysis 

3.1 

Disconnection with the  
RS232/PPI Multi--Master- Cable 

If the connection is disconnected when updating the operating system, set a lower 
baud rate.  

If you are using high baud rates, then you must use the RS232/PPI multi-master 
cable with "E-Stand 03" (development status 03) or higher. 

3.2 

Check Box Not Available in ProSave  

If the "Reset to factory settings" check box is not displayed, then recheck the 
connection settings made (

Link

). It is possible that the operator panel does not 

support the transfer type required for this option. 

Refer here to Table 2-1 in section 2.1.2 "Resetting the Operator Panel to the 
Factory Settings (Booting)". 

3.3 

Check Box Cannot be Deselected in ProSave  

If you use the "USB/PPI Multi-Master Cable" transfer type, then, depending on the 
system, on some operator panels it might not be possible to deselect the "Reset to 
factory settings" option.  
In this case, you cannot make an operating system update (OS Update) using the 
cable, but can only do a "Reset to factory settings" (reboot).  

Refer here to Table 2-1 in section 2.1.2  

 

background image

3 2BProblem Analysis 

 

 

 

16 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

Operating System Update with  
WinCC (TIA Portal)”.  

background image

3 2BProblem Analysis

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

17 

 

3.4 

Error Message during the Transfer of the Configuration  

You have changed the operating system of your operator panel and during transfer 
of the configuration you receive the message that the operating system version of 
the operator panel does not match the software version used. 

In this case, prior to updating the operating system, check that the Image path has 
been set correctly and that you have selected the correct Image file. See section 
2.2 "Set the Image Path / File in ProSave" for this.  

Sample error message in WinCC (TIA Portal). 

Figure 3-1 

 

 

3.5 

Comfort Panel "Reset to factory settings"  

If a Comfort Panel is to be reset to the factory settings, then in ProSave you get 
this prompt: "Please boot the operator panel...".  
In this case, for Comfort Panels you must select the "Prepare for Reset" function 
prior to booting, which starts updating of the operating system when the Comfort 
Panel is restarted.  

In this case refer to Entry ID: 60114889. 

3.6 

MP 377 "Reset to Factory Settings" (Booting)  

If the MP 377 operator panel cannot be reset to the factory settings, then check the 
Image version of the MP 377. 

MP 377 operator panels with the Image version installed for WinCC flexible 2008 
and higher (Image version as from V01.00.02.00_01.83) have the new parameter 
"Prepare for Reset".  

In this case refer to Entry ID: 

35677293

 

 

 

background image

3 2BProblem Analysis 

 

 

 

18 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

3.7 

A Connection to the Operator Panel Cannot be 
Established 

Some points are given below, which you should check if no connection is 
established between the operator panel and the configuration computer. 

3.7.1 

Check Transmission Type and Address on the Operator Panel 

Compare the transfer settings on the operator panel with those on the configuration 
computer. 

Example: 

Specification of configuration computer  
•  Transfer via PROFIBUS 
•  Panel address 10   
Make sure that "Panel is the only master on the bus" is checked for the transfer 
settings on the operator panel. 

Figure 3-2 

 

 

More information on the topic of "Transfer Settings" is available in Entry ID: 

23802404

  

 

background image

3 2BProblem Analysis

 

OS Update WinCC (TIA Portal) 
Version V1.0, Entry ID: 19701610 

19 

 

3.7.2 

Check Cable Connection and Connector  

MPI/PROFIBUS cable  

Please check the following points:  
•  Cable connection between the operator panel and the configuration computer. 
•  Check the cable for damage. 
•  Bus connector especially the connection of the terminating resistors. 

–  Terminating resistors ON/OFF.  

The following guideline value applies: 
•  Bus terminating resistor OFF:   

–  Bus connector with "two" cables connected. 

•  Bus terminating resistor ON:  

–  Bus connector with "one" cable connected. 

More information on the topic of "Bus terminating resistor" is available in Entry ID: 

187276

  

 

RS232/PPI multi-master cable  

When using an "RS232/PPI multi-master cable", please note the switch settings.  

More information on this topic is available in Entry ID: 

16532946

 

Ethernet cable  

Use a "crossed" Ethernet cable for the connection between a PG/PC and an 
operator panel.  

If you use a "patch" cable, you need a switch in addition.  

Note 
Operator panels with two "Ethernet interfaces" have an integrated switch. 

 

background image

3 2BProblem Analysis 

 

 

 

20 

OS Update WinCC (TIA Portal) 

Version V1.0, Entry ID: 19701610 

 

3.7.3 

Check the PG/PC Interface on the Configuration Computer 

Check the PG/PC Interface on the Configuration Computer 

In Windows XP:  

–  "Start > SIMATIC > SIMATIC NET > Set PG-PC interface". 

and 
–   "Start > Settings > Control Panel > Setting the PG/PC Interface" 

 

Check the following settings of the PG/PC interface  

•  When setting the interface parameters in 

MPI or PROFIBUS, make sure that the node address is set to "0".  

•  We also recommend that you select the "PG/PC is the only master on the bus" 

option.  

•  Check the "Transmission rate".  
•  Check the "Highest station address".  
 

Figure 3-3 

 

 