Speed control of single-phase AC motors

In order to reduce the power consumption of single-phase AC motors, their speed can be regulated as 
required. Depending on the process data, the speed can be reduced in the case of low load requirements in 
order to reduce noise emissions, increase energy efficiency and prolong the service life of the units.

Effects of the change in speed

Single-phase AC motors with square load characteristic curves are often used as additional units for fans or pumps, for 
example. As opposed to three-phase motors, no start-up optimisation is necessary as in the case of star-delta and adjustment 
to different load cases by means of a frequency converter is often not provided for. The additional units are usually switched in 
an interval orientated manner or simply activated during a certain phase of the control program. The following AC motors are 
in use, depending on the application: capacitor, universal and shaded-pole motors.

 

M

1~

L1

N

M

1~

L1

N

M

1~

L1

N

Capacitor motor

Universal motor

Shaded-pole motor

Fig. 1: Controllable AC motors on the KL2791

New Automation Technology

Beckhoff

1

For application notes see disclaimer on the last page

background image

I/O

Bus Terminal

Application Note DK9222-1009-0006

When driving working machines whose production or conveying output can be influenced via the drive speed of the motor, 
energy can be saved by means of variable speed. This particularly applies if the change in the motor speed is also linked with 
large changes in the emitted mechanical output. Increase the speed – higher load, decrease – lower load. This procedure is 
particularly suitable for uncontrolled units with a square load characteristic, because regulating the speed just a little brings 
about a large change in energy consumption due to its square influence.

Practical example
Cooling lubricant pump in a milling machine

Two frequently occurring control scenarios are illustrated here, after which the optimisation is demonstrated. The pump is 
coupled in both cases to the tool drive in order to guarantee that sufficient cooling lubrication takes place when the blades cut 
into the workpiece.

Scenario 1 

 

5

4

2

1

3

Scenario 1

Volume rate of flow

Pump

Start-up

phase

1

st

 

cut

Constant

cut

Exit

Move-out 

phase

 Tool drive active

Cooling lubricant consumption

 Energy consumption

Fig. 2 Need for optimised control  

Cooling lubrication is fundamentally required during the runtime of the miller (tool drive) in order to achieve appropriate 
surface qualities and to keep the thermal loading of the workpiece low. For this reason, the cooling lubricant circulation pump 
is linked to the tool drive in order to securely guarantee pumping. There are two operating cases for the pump: Pump on | pump 
off; therefore, no changes in the load take place. The pump always runs at full speed and with full power consumption, even 
during the phases where the tool is moving in and moving out (1 and 5), at which time the tool drive is active, but the tool 
itself is not cutting.

New Automation Technology

Beckhoff

2

For application notes see disclaimer on the last page

background image

I/O

Bus Terminal

Application Note DK9222-1009-0006

Scenario 2

 

5

4

2

1

3

Scenario 2

Volume rate of flow

Pump

Start-up

phase

1

st

 cut

Constant

cut

Exit

Move-out 

phase

 Tool drive active

Cooling lubricant consumption

 Energy consumption

Fig. 3  Fractional optimised control

Similar to the example above, the pump is linked logically to the tool drive. However, additionally, there is a valve to regulate 
the flow rate for different load cases and to prevent pumping when the tool is driving in. Although the cooling lubricant 
consumption is thus optimised, the pump is still running at 100 % utilisation, even though the flow rate is only minimal. 
Furthermore, a dynamic pressure builds up at the valve due to the constantly running pump, so that when the valve is opened 
the cooling lubricant shoots out before the normal pumping pressure has been established.

New Automation Technology

Beckhoff

3

For application notes see disclaimer on the last page

background image

I/O

Bus Terminal

Application Note DK9222-1009-0006

This publication contains statements about the suitability of our products for certain areas of application. These statements are based on typical features of our products. The examp-
les shown in this publication are for demonstration purposes only. The information provided herein should not be regarded as specific operation characteristics. It is incumbent on the 
customer to check and decide whether a product is suit-able for use in a particular application. We do not give any warranty that the source code which is made available with this 
publication is complete or accurate. This publication may be changed at any time with-out prior notice. No liability is assumed for errors and/or omissions. Our products are described 
in detail in our data sheets and documentations. Product-specific warnings and cautions must be observed. For the latest version of our data sheets and documentations please visit 
our website (www.beckhoff.com).

© Beckhoff Automation GmbH, October 2009
The reproduction, distribution and utilisation of this document as well as the communication of its contents to others without express authorisation is prohibited. Offenders will be 
held liable for the payment of damages. All rights reserved in the event of the grant of a patent, utility model or design.

Optimisation – speed control using the KL2791

In neither case the power consumption of the pump is affected; therefore, the use of the single-phase AC motor terminal makes 
sense in order to achieve a reduction in the consumed power.

 

5

4

2

1

3

KL2791

Volume rate of flow

Pump

Start-up

phase

1

st 

cut

Constant

 cut

Exit

Move-out 

phase

 Tool drive active

 Cooling lubricant consumption

 Energy consumption

Fig. 4  Optimised control with the KL2791

Using the KL2791 single-phase AC motor terminal, a single-phase AC motor with a maximum power consumption of 0.1 kW 
can be operated with speed control depending on the process data. L1 and N of the motor are wired directly to the terminal; 
this is in turn integrated in the control environment via a Bus Coupler or connected directly to an embedded device.
The controller specifies the set value for the motor speed in the form of a 16-bit word; the speed is regulated internally in the 
terminal: the motor is switched on and off with a practice-proven mains-synchronous pattern, so that the motor consumes less 
power and the speed falls significantly. This method is well suited to motors with fixed loads, such as pumps and fans, in order 
to achieve a control range for the flow rate from 10 % to 100 %.

– 1-channel AC motor speed controller, 230 V AC, 100 VA www.beckhoff.com/KL2791