Function description

D. Electrical function, control unit as of approx. 08/86 (Webasto no. 
105.499)

Note

3. Repeat start:

The following functions of this control unit 

If combustion does not occur during the 

(N33) 

first start, the combustion air blower 

have been modified or added:

continues running for 30 seconds. 
Thereafter, a second start is performed 

1. Undervoltage cutout:

automatically. If this also does not result 

If the power supply drops below 9.5 

 

in combustion, the combustion air blower 

0.5 volts during the cut-in period, the 

continues running for 60 seconds. The 
total time to a fault cut-off is increased 

auxiliary heater switches off. The 

from the previous 4 minutes to 5 1/2 

auxiliary heater can only be restarted 

minutes.

after it is switched off and on again.

4. After-running controller of combustion 

2. Glow plug monitoring:

air blower after interruption of 

If the glow coil of the glow plug or the 

combustion:

power supply is interrupted, the control 

If combustion is interrupted, e.g. because 

unit switches to fault. The combustion air 

of a shortage of fuel, a photo-transistor in 

blower continues running for approx. 60 

the flame monitor assures optically 

seconds. The operating indicator lamp 

controlled after-running of the 

then goes out and the auxiliary heater 

combustion air blower. This is limited to 

switches off. No automatic repeat start is 

max. 80 seconds. Thereafter, the 

performed as before.

electronically controlled after-running of 
60 seconds commences, as before. 

5. Temperature-switching points

Coolant temperature in heater (°C)

Full load to part load

78

Part load to full load

70

Start of combustion interval

86

End of combustion interval (full-load start)

78