background image

 

1                         SERVICE MANUAL FOR CMV 

DC Inverter Multi-Split Air-Condition Unit   

 

                                                                                   

 

                                                           

                                                                                   

                                                                                                                            CMV-71V3A-T 

                                                                                                                            CMV-V80WC3AQ 

 

 

 

 

 

 

                                                                                                                                  CMV-50V3A-E2 

 

 

 

 

 

                                                                                                                                  CMV-V40H13AD 

 

REFRIGERENT 

R410A 

HEAT PUMP 

SERVICE

MANUAL

background image

 

2                         SERVICE MANUAL FOR CMV

 

 

Table of Contents

 

1. INTRODUCTION .................................................................................................1-1 

2. PRODUCT 

DATA SHEET  ...................................................................................2-1 

3. RATING 

CONDITIONS  ........................................................................................3-1 

4. OUTLINE 

DIMENSIONS  .....................................................................................4-1 

5. PERFORMANCE 

DATA ......................................................................................5-1 

6. PRESSURE 

CURVES  .........................................................................................6-1 

7. ELECTRICAL DATA .............................................................................................7-1 

8. WIRING 

DIAGRAMS  ...........................................................................................8-1 

9. REFRIGERATION 

DIAGRAMS  ...........................................................................9-1 

10. TUBING 

CONNECTIONS .....................................................................................10-1 

11. CONTROL 

SYSTEM ...........................................................................................11-1 

12. TROUBLESHOOTING ........................................................................................12-1 

13.  EXPLODED VIEWS AND SPARE PARTS LISTS ................................................13-1 

14. APPENDIX 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

background image

 

3                         SERVICE MANUAL FOR CMV

 

1. INTRODUCTION 

 

1.1 General 

The new CMV is a high efficiency DC inverter technology outdoor unit, 
since it’s a lego concept unit, it can be matched to several inverter indoor units such as wall 
mounted type with a capacity range of 2.0 – 5.0 Kw for each single indoor unit. 

 

1.2 Main 

Features 

DC Inverter 

R410a 
sine wave form and 120 degree rectangurlar wave form in comprssor driver 
sensor less inverter compressor driver 
high speed calculation for accurate sine wave form vector control 
smart PFC control 
fuzzy logic con

trol

 

High COP (“A “ or “B” class energy rating) 
Lego Concept 
Pre-Charged

.

 

Cooling operation at outdoor temperature down to 10

0

C. 

Heating operation at outdoor temperature down to -15

0

C. 

Variable Speed outdoor fan. 
Low noise level 
EEV for each indoor unit 

1.3 Tubing Connections 

Flare type interconnecting tubing to be produced on site. 
For further details please refer to APPENDIX A on this manual, and to the relevant indoor 
service Manual, 
 

1.4 Inbox Documentation 

Each indoor unit is supplied with its own installation and operation manuals. 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

background image

 

4                         SERVICE MANUAL FOR CMV

 

2 .  

P R O D U C T   D A T A   S H E E T  

2 . 1 . 1  

O u t d o o r   U n i t   C M V - 5 0 V 3 A - E 2   S p e c i f i c a t i o n s .  

OUTDOOR UNNIT 

Model 

CMV-50V3A-E2 

Operation Model 

Cooling 

Heating 

Kcal/hr 

4300(1032-5848) 

5160(860-6278) 

Btu/hr 

17064(4095-23207) 

20477(3412-24913) 

Capacity 

5000(1400-6800) 

6000(1300-7300) 

Total Input 

1400(460-2300) 

1600(450-2200) 

E.E.R(Cooling)/C.O.P(Heating) 

W/W 

3.57 

3.75 

Starting Current 

Inrush Current 

<35 

Power Supply 

V/PH/Hz 

220-240V 1PH 50Hz 

Refrigerant control 

   

Electronic expansion valve 

Compressor Type 

   

Twin Rotary DC Inverter 

Model 

   

C-6RZ146H1A 

Starter Type 

   

  Low frequency start 

Protection Device 

   

Outdoor SW control 

Heat Exchanger 

   

Hydrophilic corrugated fins ,Grooved tube 

Fan×No. 

   

Propeller×1 

Airflow 

m

3

/hr 

2450 

Motor Output 

60 

Defrost method 

   

Reverse cycle 

Pressure 

55 

55 

Noise Level 

Power 

dB(A) 

65 

65 

Dimensions 

W*D*H 

mm 

850×292×607 

Weight 

Kg 

50 

Package 

W*D*H 

mm 

995×415×680 

O

U

TDOO

R UN

NI

T

 

Unit Stacking 

Refrigerant Charge 

R410A-1580g 

Liquid 

mm 

2×6.35 

Tube Size O.D 

Suction 

mm 

2×9.52 

Indoor  & outdoor 

Flared 

Height difference betweeen indoor unit 

Max.10m 

Height difference betweeen indoor  & outdoor

Max.10m 

Tubing length 

Max.20m for one unit and 30m total 

TUBING

 

Connection method 
between the indoor 
and the outdoor 
units 

Additional charge 

No need   

 

 

 

 

 

 

background image

 

5                         SERVICE MANUAL FOR CMV

 

2 . 1 . 2   O u t d o o r  

U n i t  

C M V - 7 1 V 3 A - T   S p e c i f i c a t i o n s .  

OUTDOOR UNIT 

Model 

CMV-71V3A-T 

Operation Model 

Cooling 

Heating 

Kcal/hr 

6106(1290-7998) 

7740(1118-9030) 

Btu/hr 

24231(5118-31731) 

30708(4435-35826) 

Capacity 

7100(1500-9000) 

8500(1700-10500) 

Total Input 

2200(580-3200) 

2330(540-3000) 

E.E.R(Cooling)/C.O.P(Heating) 

W/W 

3.227 

3.648 

Starting Current 

Inrush Current 

<35 

Power Supply 

V/PH/Hz 

220-240V 1PH 50Hz 

Refrigerant control 

   

Electronic expansion valve 

Compressor Type 

   

Twin Rotary DC Inverter 

Model 

   

C-7RVN153HOW 

Starter Type 

   

  Low frequency start 

Protection Device 

   

Outdoor SW control 

Heat Exchanger 

   

Hydrophilic corrugated fins ,Grooved tube 

Fan×No. 

   

Propeller×1 

Airflow 

m

3

/hr 

3200 

Motor Output 

90 

Defrost method 

   

Reverse cycle 

Pressure 

57 

57 

Noise Level 

Power 

dB(A) 

65 

65 

Dimensions 

W*D*H 

mm 

960×344×846 

Weight 

Kg 

82 

Package 

W*D*H 

mm 

1060×470×925 

O

U

TDOO

R UN

NI

T

 

Unit Stacking 

Refrigerant Charge 

R410A-3,000 

Liquid 

mm 

3×6.35 

Tube Size O.D 

Suction 

mm 

2×9.52+1×12.7 

Indoor  & outdoor 

Flared 

Height difference betweeen indoor unit 

Max.15m 

Height difference betweeen indoor  & 
outdoor 

Max.15m 

Tubing length 

Max.25m for one unit and 50m total 

TUBING

 

Connection method 
between the indoor 
and the outdoor units 

Additional charge 

No need 

 

 

 

 

 

 

background image

 

6                         SERVICE MANUAL FOR CMV

 

2 . 1 . 3   O u t d o o r  

U n i t  

C M V - V 8 0 W C 3 A Q   S p e c i f i c a t i o n s .  

OUTDOOR UNNIT 

Model 

CMV-V80WC3AQ 

Operation Model 

Cooling 

Heating 

Kcal/hr 

6880(1720-7740) 

8256(1720-9460) 

Btu/hr 

27296(6824-30708) 

32755(6824-37532) 

Capacity 

8000(2000-9000) 9600(2000-11000) 

Total Input 

2450(710-3350) 

2400(910-2950) 

E.E.R(Cooling)/C.O.P(Heating) 

W/W 

3.26 

Starting Current 

Inrush Current 

<35 

Power Supply 

V/PH/Hz 

220-240V 1PH 50Hz 

Refrigerant control 

   

Electronic expansion valve 

Compressor Type 

   

Twin Rotary DC Inverter 

Model 

   

C-7RVN153HOW 

Starter Type 

   

Low frequency start 

Protection Device 

   

Outdoor SW control 

Heat Exchanger 

   

Hydrophilic corrugated fins ,Grooved tube 

Fan×No. 

   

Propeller×1 

Airflow 

m

3

/hr 

3200 

Motor Output 

90 

Defrost method 

   

Reverse cycle 

Pressure 

57 

57 

Noise Level 

Power 

dB(A) 

65 

65 

Dimensions 

W*D*H 

960×344×846

960×344×846 

Weight 

Kg 

86 

Package 

W*D*H 

1060×470×925

1060×470×925 

O

U

TDOO

R UN

NI

Unit Stacking 

Refrigerant Charge 

R410A-3,600g 

Liquid 

mm 

4×6.35 

Tube Size O.D 

Suction 

mm 

3×9.52+12.7 

Indoor  & outdoor 

Flared 

Height difference betweeen 
indoor unit 

Max.10m 

Height difference betweeen 
indoor  & outdoor 

Max.10m 

Tubing length 

Max.25m for one unit and 70m total 

TUBING 

Connection method 
between the indoor 
and the outdoor units 

Additional charge 

No need   

 

 

 

 

background image

 

7                         SERVICE MANUAL FOR CMV

 

2 . 1 . 4  

O u t d o o r   U n i t   C M V - V 4 0 H 1 3 A D   S p e c i f i c a t i o n s .  

OUTDOOR UNNIT 

Model 

CMV-V40H13AD 

Operation Model 

Cooling 

Heating 

Kcal/hr 

3430(1250-4460) 

4000(1300-4600) 

Btu/hr 

13700(5000-17800) 

15700(5200-18100) 

Capacity 

4000(1450-5200) 

4600(1500-5300) 

Total Input 

1020(450-1580) 

1050(430-1300) 

E.E.R(Cooling)/C.O.P(Heating) 

W/W 

3.92 

4.38 

Starting Current 

Inrush Current 

<15 

Power Supply 

V/PH/Hz 

220-240V 1PH 50Hz 

Refrigerant control 

   

Electronic expansion valve 

Compressor Type 

   

Single Rotary DC Inverter 

Model 

   

5RS102XCA01 

Starter Type 

   

  Low frequency start 

Protection Device 

   

Outdoor SW control 

Heat Exchanger 

   

Hydrophilic corrugated fins ,Grooved tube 

Fan×No. 

   

Propeller×1 

Airflow 

m

3

/hr 

1800 

Motor Output 

35 

Defrost method 

   

Reverse cycle 

Pressure 

53 

53 

Noise Level 

Power 

dB(A) 

65 

65 

Dimensions 

W*D*H 

mm 

860×320×550 

Weight 

Kg 

50 

Package 

W*D*H 

mm 

905×323×573 

O

U

TDOO

R UN

NI

T

 

Unit Stacking 

Refrigerant Charge 

R410A-1250g 

Liquid 

mm 

2×6.35 

Tube Size O.D 

Suction 

mm 

2×9.52 

Indoor  & outdoor 

Flared 

Height difference betweeen indoor unit 

Max.10m 

Height difference betweeen indoor  & outdoor

Max.10m 

Tubing length 

Max.20m for one unit and25m total 

TUBING

 

Connection method 
between the indoor 
and the outdoor 
units 

Additional charge 

No need   

 

 

 

 

 

 

 

background image

 

8                         SERVICE MANUAL FOR CMV

 

 

2 . 2  

I n d o o r   U n i t s   D a t a  

2 . 2 . 1   C M V S - 2 5 V 3 A - A 4 8 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-25V3A-A48A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

870×350×270 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

 

2 . 2 . 2   C M V S - 3 5 V 3 A - A 4 8 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-35V3A-A48A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

870×350×270 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

background image

 

9                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 3  

C M V S - 2 5 V 3 A - A 3 8 A     C M V S - 2 5 V 3 A - A 3 8 B     S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-25V3A-A38A 

CMVS-25V3A-A38B 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

880×360×250 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 4  

C M V S - 3 5 V 3 A - A 3 8 A     C M V S - 3 5 V 3 A - A 3 8 B  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-35V3A-A38A 

CMVS-35V3A-A38B 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

880×360×250 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

background image

 

10                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 5   C M V S - 2 5 V 3 A - A 4 6 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-25V3A-A46A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

870×350×270 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 6   C M V S - 3 5 V 3 A - A 4 6 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-35V3A-A46A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

870×350×270 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

background image

 

11                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 7   C M V S - 2 5 V 3 A - A 6 9 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-25V3A-A69A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 8   C M V S - 3 5 V 3 A - A 6 9 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-35V3A-A69A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

background image

 

12                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 9   C M V - V 2 5 G 3 A / A 6 7  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V25G3A/A67 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 1 0  

C M V - V 3 5 G 3 A / A 6 7     S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V35G3A/A67 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

background image

 

13                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 1 1   C M V - V 2 5 G 3 A / A 7 8  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V25G3A/A78 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 1 2  

C M V - V 3 5 G 3 A / A 7 8     S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V35G3A/A78 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

background image

 

14                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 1 3   C M V - V 2 0 G 3 A / G 3 8 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V20G3A/G38A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

450 

350 

Airflow Cooling/Heating 

m

3

/hr 

270 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

Packaging Dimensions 

W/H/D 

mm 

880×360×250 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.6 

 

 

2 . 2 . 1 4   C M V - V 5 0 G 3 A / H 3 8 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V50G3A/H38A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

930×270×180 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1010×360×280 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

 

background image

 

15                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 1 5   C M V S - 5 0 V 3 A - N 4 6 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-50V3A-N46A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

998×320×210 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1085×380×300 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

2 . 2 . 1 6   C M V S - 5 0 V 3 A - N 1 7 A  

S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMVS-50V3A-N17A 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

1015×320×204 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1085×380×300 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

 

background image

 

16                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 1 7     C M V - V 2 5 G 3 A / M 8 5  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V25G3A/M85 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level 
Cooling/Heating 

L-H 

dB(A) 

29-39 

Condensate Drain Tube I.D 

mm 

16 

Dimensions 

W/H/D 

mm 

800×280×187 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

860×350×265 

IN

D

OOR 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.6 

 

2 . 2 . 1 8     C M V - V 3 5 G 3 A / M 8 5  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V35G3A/M85 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

480 

Airflow Cooling/Heating 

m

3

/hr 

380 

  Sound Preesure Level 
Cooling/Heating 

L-H 

dB(A) 

29-39 

Condensate Drain Tube I.D 

mm 

16 

Dimensions 

W/H/D 

mm 

800×280×187 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

860×350×265 

IN

D

OOR 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

 

 

background image

 

17                         SERVICE MANUAL FOR CMV

 

2 . 2 . 1 9     C M V - V 2 5 G 3 A / A 2 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V25G3A/A27 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 2 0     C M V - V 3 5 G 3 A / A 2 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V35G3A/A27 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

 

background image

 

18                         SERVICE MANUAL FOR CMV

 

2 . 2 . 2 1     C M V - V 2 5 G 3 A / A 7 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V25G3A/A77 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

500 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

0.8 

 

2 . 2 . 2 2     C M V - V 3 5 G 3 A / A 7 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V35G3A/A27 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

550 

450 

Airflow Cooling/Heating 

m

3

/hr 

360 

Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

32-41/32-41 

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

270×180×790 

Weight 

   

kg 

12 

Packaging Dimensions 

W/H/D 

mm 

875×338×285 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

 

 

 

background image

 

19                         SERVICE MANUAL FOR CMV

 

2 . 2 . 2 3     C M V - V 5 0 G 3 A / H 2 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V50G3A/H27 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

930×270×180 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1010×360×280 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

 

2 . 2 . 2 3     C M V - V 5 0 G 3 A / H 7 7  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V50G3A/H77 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

930×270×180 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1010×360×280 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

 

background image

 

20                         SERVICE MANUAL FOR CMV

 

 

2 . 2 . 2 4     C M V - V 5 0 G 3 A / H 4 8  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V50G3A/H48 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

930×270×180 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1010×360×280 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

 

2 . 2 . 2 5     C M V - V 5 0 G 3 A / H 6 9  S p e c i f i c a t i o n s  

INDOOR UNIT 

Model Indoor Unit/Type 

CMV-V50G3A/H69 

Installation method 

Flare 

Power Supply 

V/Ph/Hz 

220-240/1/50 

Fan Type & Quantity 

Crossflow×1 

750 

550 

Airflow Cooling/Heating 

m

3

/hr 

450 

  Sound Preesure Level Cooling/Heating 

L-H 

dB(A) 

35-43/35-43   

Condensate Drain Tube I.D 

   

mm 

16 

Dimensions 

W/H/D 

mm 

930×270×180 

Weight 

   

kg 

14 

Packaging Dimensions 

W/H/D 

mm 

1010×360×280 

IN

D

OOR

 

Stacking Height 

   

Units 

Heating Elements 

   

KW 

N/A 

Moisture Removal 

   

L/hr 

1.2 

 

 

background image

 

21                         SERVICE MANUAL FOR CMV

 

3 .   R A T I N G  

C O N D I T I O N S  

Standard conditions in accordance with ISO 5151, and EN 14511. 

Cooling: 
Indoor:  27

o

C DB 19

o

C WB 

Outdoor: 35

 o

C DB 24

o

C WB 

Heating: 
Indoor:  20

o

C DB 15

o

C WB 

Outdoor:  7

 o

C DB 6

 o

C WB 

3 . 1   O p e r a t i n g  

L i m i t s  

   

Outdoor 

Upper limit  (DB) 

46

o

C  

Cooling 

Lower limit  (DB) 

10

o

C  

Upper limit  (DB) 

24

o

C  

Heating 

Lower limit  (DB) 

-15

o

C  

2PH 198–264V 

Voltage 

3PH N/A 

 

 

 

 

 

 

 

 

background image

 

22                         SERVICE MANUAL FOR CMV

 

4 .   O U T L I N E  

D I M E N S I O N S  

4.1  outdoor Unit: CMV-V40H13AD 

 

 

4.2  outdoor Unit: CMV-50V3A-E2

 

 

 

 

 

 

 

 

 

 

 

background image

 

23                         SERVICE MANUAL FOR CMV

 

4.3 outdoor Unit: CMV-V80WC3AQ, CMV-71V3A-T 

560

37

8

34

2

84

5

35

1

72

50

956

82

5

50

×3

(=1

50)

50

 

5 .   P E R F O R M A N C E  

D A T A  

  

5 . 1           O u t d o o r  u n i t s  d a t a  

5 . 1 . 1      

CMV-V40H13AD

  C o m b i n a t i o n s ( b a s e d   o n   s p l i t   i n d o o r   u n i t s )  

Data For Outdoor Unit CMV-V40H13AD Combinations (Based on Split indoor units)

Cooling 

Heating 

RoomA  RoomB 

Total 

Capacity 

Power 
Input 

RoomA

RoomB

Total 

Capacity 

Power Input

Indoor Units 
Combinations 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

20 

2000 

2000     

(1450-3200)

540     

(450-1050)

2500

2500    

(1500-3200) 

690      

(430-940) 

25 

2500 

2500   

(1450-3350)

710   

(450-1140)

3000

3000   

(1500-3400) 

840      

(430-990) 

35 

3500 

3500   

(1450-4700)

1020   

(450-1250)

3500

3500   

(1450-3800) 

950      

(450-1100) 

20+20 

2000 

2000 

4000   

(1450-5200)

1020   

(450-1550)

2300

2300

4600  

(1500-5050) 

1050     

(430-1300) 

20+25S 

2000 

2500 

4500   

(1450-5200)

1250  

(450-1570)

2265

2835

5100  

(1500-5300) 

1250     

(430-1320) 

25S+25S 

2500 

2500 

5000   

(1450-5200)

1470  

(450-1610)

2600

2600

5200  

(1500-5300) 

1270     

(430-1350) 

25S+35 

2100 

2950 

5050   

(1450-5250)

1480  

(450-1620)

2200

3100

5300  

(1500-5400) 

1290     

(430-1380) 

 

background image

 

24                         SERVICE MANUAL FOR CMV

 

5 . 1 . 2    

CMV-50V3A-E2

  C o m b i n a t i o n s ( b a s e d   o n   s p l i t   i n d o o r   u n i t s )

 

Data For Outdoor Unit CMV-50V3A-E2 Combinations (Based on Split indoor units) 

Cooling 

Heating 

RoomA  RoomB 

Total 

Capacity 

Power Input

RoomA

RoomB

Total 

Capacity 

Power 
Input 

Indoor Units 
Combinations 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

20 

2000 

2000     

(1420-2960)

650     

(460-950) 

2500 

2500    

(1280-3300) 

710     

(420-980)

25 

2600 

2600     

(1420-3700)

660     

(460-990) 

3200 

3200    

(1280-3700) 

880     

(420-1020)

35 

3500 

3500   

(1420-4350)

1010   

(460-1280)

4200 

4200   

(1300-5200) 

1160     

(435-1420)

20+20 

2150 

2150 

4300   

(1600-6150)

1320   

(460-2100)

2550 

2550

5100  

(1300-6850) 

1480     

(450-2130)

20+25 

2050 

2550 

4600   

(1600-6400)

1380   

(460-2130)

2450 

3050

5500  

(1300-7000) 

1470     

(450-2100)

25+25 

2600 

2600 

5200   

(1600-6800)

1400   

(460-2250)

3000 

3000

6000  

(1300-7300) 

1600     

(450-2200)

20+35 

2040 

3050 

5600   

(1600-6850)

1750   

(460-2250)

2450 

3050

6200  

(1300-7300) 

1700     

(450-2200)

25+35 

2450 

3450 

5900   

(1600-6850)

1820   

(460-2260)

3100 

3450

6550  

(1300-7350) 

1850     

(450-2220)

35+35 

3100 

3050 

6150   

(1600-6880)

1890   

(460-2270)

3450 

3450

6900  

(1300-7400) 

1890     

(450-2220)

 

 

 

 

5 . 1 . 3     C M V - 7 1 V 3 A - T     C o m b i n a t i o n s ( b a s e d  o n  s p l i t  i n d o o r  u n i t s )  

Data For Outdoor Unit CMV-71V3A-T Combinations 

(Based on Split indoor units)

 

Cooling 

Heating 

RoomA  RoomB

RoomC 

Total 

Capacity 

Power 
Input 

RoomA

RoomB

RoomC 

Total 

Capacity 

Power 
Input 

Indoor Units 
Combinations 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

20 

2000 

2000     

(1500-2960)

665     

(580-950)

2500 

2500     

(1700-3300)

720     

(540-940)

25 

2500 

2500     

(1500-3700)

785     

(580-1125)

3000 

3000     

(1700-3700)

810     

(540-1030)

26 

2600 

2600     

(1500-3700)

785     

(580-1125)

3000 

3000     

(1700-3700)

810     

(540-1030)

35 

3500 

3500    

(1600-4350)

1070     

(580-1330)

4300 

4300     

(2000-5200)

1160    

(610-1410) 

50 

5000 

5000    

(1900-5930)

1490    

(580-1790)

6000 

6000    

(2300-6800)

1600    

(690-1860)

20+20 

2000 

2000 

4000    

(1500-5140)

1250    

(580-1650)

2800

2800 

5600    

(2100-6800)

1550    

(540-1950)

20+26 

2000 

2600 

4600    

(1500-5630)

1350    

(580-1850)

2600

3200 

5800    

(2200-7300)

1600    

(540-2050)

20+35 

1900 

3200 

5100    

(1500-6100)

1550    

(580-2010)

2600

3500 

7100    

(2200-7700)

1950    

(540-2250)

20+50 

1860 

4640 

6500   

(1500-8700)

2100    

(580-2900)

2450

6050 

8500    

(1700-9300)

2320    

(540-2660)

background image

 

25                         SERVICE MANUAL FOR CMV

 

25+25 

2520 

2520 

5040    

(1500-6000)

1480    

(580-1770)

3000

3000 

6000    

(1700-7700)

1590    

(540-2090)

25+35 

2510 

3390 

5900    

(1500-7000)

1780    

(580-2160)

3100

4240 

7340    

(1700-8300)

1990     

(540-2270)

25+50 

2350 

4880 

7030    

(1500-8900)

2150    

(580-2960)

2900

5800 

8700    

(1700-9400)

2370    

(540-2660)

26+26 

2520 

2520 

5040    

(1500-6000)

1480    

(580-1770)

3000

3000 

6000    

(1700-7700)

1590    

(540-2090)

26+35 

2550 

3350 

5900    

(1500-7000)

1780    

(580-2160)

3140

4200 

7340    

(1700-8300)

1990    

(540-2270)

26+50 

2410 

4620 

7030    

(1500-8900)

2150    

(580-2960)

3000

5700 

8700    

(1700-9400)

2370    

(540-2660)

35+35 

3450 

3450 

6900   

(1600-8600)

2120    

(580-2860)

3900

3900 

7800    

(2000-8800)

2150    

(610-2400)

35+50 

2960 

4280 

7040    

(1600-8900)

2150    

(580-2960)

3400

5400 

8800    

(1700-9500)

2400    

(540-2670)

20+20+20 

2115 

2115 

2120 

6350    

(1500-8500)

1980    

(580-2900)

2810

2790

2790 

8390    

(1700-9800)

2330    

(540-3010)

20+20+26 

2000 

2000 

2600 

6600    

(1500-8700)

2050    

(580-2900)

2545

2545

3310 

8400    

(1700-9850)

2320    

(540-3010)

20+20+35 

1840 

1840 

3220 

6900    

(1500-8700)

2100    

(580-2900)

2250

2250

3950 

8450    

(1700-9900)

2330    

(540-3000)

20+20+50 

1575 

1575 

3950 

7100    

(1500-8900)

2210    

(580-2950)

1875

1875

4750 

8500    

(1700-10350)

2360    

(540-3000)

20+26+26 

1900 

2450 

2450 

6800    

(1500-8800)

2090    

(580-2920)

2350

3050

3050 

8450    

(1700-10400)

2300    

(540-3000)

20+26+35 

1760 

2300 

3040 

7100    

(1500-8800)

2200    

(580-2930)

2150

2760

3690 

8600    

(1700-10500)

2350    

(540-3000)

20+26+50 

1500 

1950 

3700 

7150    

(1500-9000)

2210    

(580-2980)

1800

2350

4500 

8650    

(1700-10600)

2380    

(540-3010)

20+35+35 

1580 

2760 

2760 

7100    

(1500-8850)

2210    

(580-2940)

1900

3350

3350 

8600    

(1700-10400)

2380    

(540-3000)

20+35+50 

1370 

2400 

3420 

7190    

(1500-9000)

2220    

(580-2980)

1660

2900

4140 

8700    

(1700-10500)

2390    

(540-3020)

25+25+25 

2350 

2350 

2400 

7100    

(1500-9000)

2200    

(580-2980)

2820

2820

2860 

8500      

(1700-10500)

2330    

(540-3000)

25+25+35 

2200 

2200 

2830 

7230    

(1500-9000)

2250    

(580-2970)

2500

2500

3700 

8700   

(1700-10500)

2380    

(540-3000)

25+25+50 

1810 

1810 

3630 

7250    

(1500-9000)

2260    

(580-2990)

2150

2150

4400 

8700    

(1700-10700)

2400    

(540-3010)

25+35+35 

1950 

2650 

2650 

7250    

(1500-9000)

2260    

(580-2970)

2400

3150

3150 

8700    

(1700-10500)

2380    

(540-3000)

25+35+50 

1660 

2230 

3370 

7260    

(1500-9000)

2280    

(580-2990)

2020

2760

4020 

8800    

(1700-10700)

2410    

(540-3020)

26+26+26 

2365 

2365 

2370 

7100    

(1500-9000)

2200    

(580-2980)

2840

2830

2830 

8500    

(1700-10500)

2330    

(540-3000)

26+26+35 

2160 

2160 

2910 

7230    

(1500-9000)

2250    

(580-2970)

2600

2600

3500 

8700    

(1700-10500)

2380    

(540-3000)

26+26+50 

1850 

1850 

3550 

7250    

(1500-9000)

2260    

(580-2990)

2220

2220

4260 

8700    

(1700-10700)

2400    

(540-3010)

26+35+35 

1950 

2650 

2650 

7250    

(1500-9000)

2260    

(580-2970)

2400

3150

3150 

8700    

(1700-10500)

2380    

(540-3000)

26+35+50 

1700 

2300 

3280 

7280    

(1500-9000)

2270    

(580-2990)

2060

2780

3960 

8800    

(1700-10700)

2410    

(540-3020)

35+35+35 

2410 

2410 

2410 

7230    

(1500-9000)

2270   

(580-2980)

2850

2850

2850 

8550    

(2000-10500)

2340    

(610-3000)

 

 

 

 

 

 

background image

 

26                         SERVICE MANUAL FOR CMV

 

5 . 1 . 4     C M V - V 8 0 W C 3 A Q     C o m b i n a t i o n s ( b a s e d  o n  s p l i t  i n d o o r  u n i t s )  

Data For Outdoor Unit CMV-V80WC3AQ Combinations 

(Based on Split indoor units)

 

Cooling 

Heating 

RoomA  RoomB  RoomC  RoomD 

Total 

Capacity

Power 
Input 

RoomA

RoomB

RoomC  RoomD 

Total 

Capacity 

Power 
Input 

Indoor Units 
Combinations 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

[W] 

20 

2000 

2000  

(1800-2960)

720    

(710-1050)

2800 

2800     

(2000-3300)

930     

(910-1050)

26 

2600 

2600    

(1800-3700)

785     

(710-1200)

3200 

3200    

(2000-3700)

970     

(910-1170)

35 

3500 

3500    

(1800-4300)

1050     

(710-1400)

4300 

4300     

(2000-5200)

1210    

(910-1630) 

50 

5000 

5000    

(1800-5900)

1530    

(710-1890)

6000 

6000    

(2200-6800)

1660    

(890-1920)

20+20 

2175 

2175 

4350  

(1800-5800)

1350   

(710-1890)

2850 

2850 

5700   

(2000-6700)

1580    

(910-1950)

20+26 

2000 

2600 

4600  

(1800-5800)

1430   

(710-1900)

2520 

3280 

5800   

(2000-7000)

1610    

(910-1950)

20+35 

2000 

3500 

5500  

(1800-6300)

1700   

(710-2050)

2220 

3880 

6100   

(2000-8000)

1690    

(910-2270)

20+50 

1970 

4930 

6900  

(1800-8500)

2150   

(710-2950)

2370 

5930 

8300   

(2000-8500)

2250    

(910-2400)

26+26 

2600 

2600 

5200   

(1800-6000)

1510    

(710-1920)

3000 

3000 

6000    

(2000-7000)

1580    

(910-1990)

26+35 

2590 

3490 

6080    

(1800-6800)

1840    

(710-2200)

2680 

3600 

6280    

(2000-8200)

1680   

(910-2260)

26+50 

2390 

4610 

7000    

(1800-8600)

2170    

(710-3020)

2900 

5590 

8490    

(2000-8900)

2210    

(910-2400)

35+35 

3430 

3430 

6860     

(1800-8450)

2130     

(710-2880)

4040 

4040 

8080   

(2000-8500)

1920   

(910-2340)

35+50 

2910 

4160 

7070    

(1800-8700)

2180     

(710-3050)

3570 

5110 

8680   

(2000-8900)

2240  

(910-2480)

20+20+20 

2130 

2130 

2140 

6400  

(1800-8600)

2000   

(710-3050)

2780 

2780 

2790 

8350   

(2000-8900)

2300  

(910-2600)

20+20+26 

2000 

2000 

2600 

6600  

(1800-8600)

2050   

(710-3040)

2545 

2545 

3310 

8400   

(2000-8900)

2290  

(910-2600)

20+20+35 

1890 

1890 

3320 

7100  

(1800-8600)

2200   

(710-3050)

2255 

2255 

3940 

8450   

(2000-8900)

2290  

(910-2600)

20+20+50 

1620 

1620 

4060 

7300  

(1800-8900)

2280   

(710-3080)

1900 

1900 

4750 

8550   

(2000-9200)

2280  

(910-2650)

20+26+26 

1960 

2545 

2545 

7050  

(1800-8600)

2200   

(710-3030)

2330 

3035 

3035 

8400   

(2000-9000)

2280  

(910-2550)

20+26+35 

1800 

2340 

3160 

7300  

(1800-8700)

2270   

(710-3040)

2110 

2745 

3695 

8550   

(2000-9000)

2270  

(910-2530)

20+26+50 

1520 

1980 

3800 

7300  

(1800-8900)

2280   

(710-3100)

1800 

2340 

4510 

8650   

(2000-9700)

2250  

(910-2650)

20+35+35 

1620 

2840 

2840 

7300  

(1800-8800)

2280   

(710-3080)

1910 

3345 

3345 

8600   

(2000-8900)

2260  

(910-2620)

20+35+50 

1410 

2470 

3520 

7400  

(1800-9000)

2300   

(710-3090)

1660 

2900 

4140 

8700   

(2000-9700)

2250  

(910-2670)

26+26+26 

2400 

2400 

2400 

7200    

(1800-9000)

2250     

(710-3160)

2940 

2940 

2940 

8820   

(2000-9200)

2250  

(850-2580)

26+26+35 

2200 

2200 

2970 

7370    

(1800-9000)

2260     

(710-3160)

2640 

2640 

3550 

8830   

(2000-9300)

2250  

(850-2580)

26+26+50 

1905 

1905 

3670 

7480    

(1800-9100)

2300     

(710-3180)

2260 

2260 

4350 

8870   

(2000-9800)

2270  

(850-2650)

26+35+35 

2010 

2705 

2705 

7420    

(1800-9000)

2290     

(710-3160)

2400 

3225 

3225 

8850   

(2000-9350)

2260  

(850-2610)

26+35+50 

1840 

2480 

3540 

7860    

(1800-9100)

2320     

(710-3190)

2080 

2805 

4005 

8890   

(2000-9800)

2280  

(850-2660)

35+35+35 

2570 

2570 

2570 

7710    

(1800-9040)

2300     

(710-3200)

2960 

2960 

2970 

8890   

(2000-10200)

2270  

(850-2780)

35+35+50 

2305 

2305 

3290 

7900    

(1800-9100)

2330     

(710-3190)

2595 

2595 

3710 

8900   

(2000-10200)

2280  

(850-2780)

20+20+20+20 

1920 

1920 

1920 

1920 

7680    

(1800-9300)

2400     

(710-3290)

2300 

2300 

2300 

2300 

9200   

(2000-10600)

2550  

(850-3100)

20+20+20+26 

1800 

1800 

1800 

2350 

7750    

(1800-9300)

2420     

(710-3290)

2160 

2160 

2160 

2820 

9300   

(2000-10700)

2530  

(850-3100)

background image

 

27                         SERVICE MANUAL FOR CMV

 

20+20+20+35 

1650 

1650 

1650 

6190 

7840    

(1800-9300)

2440     

(710-3290)

1970 

1970 

1970 

3440 

9350   

(2000-10700)

2530  

(850-3100)

20+20+20+50 

1430 

1430 

1430 

3590 

7880    

(1800-9350)

2460     

(710-3300)

1720 

1720 

1720 

4290 

9450   

(2000-11000)

2520  

(850-3050)

20+20+26+26 

1700 

1700 

2215 

2215 

7830    

(1800-9300)

2440     

(710-3290)

2075 

2075 

2700 

2700 

9550   

(2000-11000)

2500  

(850-3050)

20+20+26+35 

1565 

1565 

2030 

2740 

7900    

(1800-9300)

2460     

(710-3290)

1905 

1905 

2480 

3340 

9630   

(2000-11000)

2500  

(850-3050)

20+20+25+50 

1390 

1390 

1740 

3480 

8000    

(1800-9350)

2490     

(710-3300)

1690 

1690 

2105 

4215 

9700   

(2000-11000)

2490  

(850-3050)

20+20+35+35 

1450 

1450 

2550 

2550 

8000    

(1800-9300)

2480     

(710-3290)

1760 

1760 

3080 

3080 

9680   

(2000-11000)

2500  

(850-3050)

20+20+35+50 

1310 

1310 

2240 

3240 

8100    

(1800-9400)

2520     

(710-3300)

1560 

1560 

2720 

3890 

9730   

(2000-11000)

2490  

(850-3050)

20+26+26+26 

1600 

2100 

2100 

2100 

7900    

(1800-9400)

2460     

(710-3290)

1970 

2560 

2560 

2560 

9650   

(2000-11000)

2490  

(850-3050)

20+26+26+35 

1480 

1935 

1935 

2600 

7950    

(1800-9400)

2480     

(710-3290)

1810 

2350 

2350 

3170 

9680   

(2000-11000)

2490  

(850-3050)

20+26+26+50 

1300 

1725 

1725 

3300 

8050    

(1800-9400)

2510     

(710-3300)

1585 

2070 

2070 

3975 

9700   

(2000-11000)

2480  

(850-3050)

20+26+35+35 

1380 

1790 

2400 

2400 

7970    

(1800-9400)

2490     

(710-3290)

1670 

2170 

2925 

2925 

9690   

(2000-11000)

2470  

(850-3050)

20+26+35+50 

1230 

1600 

2150 

3080 

8060    

(1800-9400)

2510     

(710-3350)

1480 

1925 

2590 

3705 

9700   

(2000-11000)

2470  

(850-3050)

20+35+35+35 

1310 

2250 

2250 

2250 

8020    

(1800-9400)

2490     

(710-3350)

1555 

2715 

2715 

2715 

9700   

(2000-11000)

2460  

(850-3050)

25+25+25+25 

2000 

2000 

2000 

2000 

8000     

(1800-9400)

2450     

(710-3350)

2400 

2400 

2400 

2400 

9600   

(2000-11000)

2400  

(910-3050)

25+25+25+35 

1870 

1870 

1870 

2490 

8100     

(1800-9400)

2470     

(710-3350)

2195 

2195 

2195 

3065 

9650   

(2000-11000)

2400  

(910-3050)

25+25+25+50 

1610 

1610 

1610 

3280 

8110     

(1800-9400)

2480     

(710-3350)

1950 

1950 

1950 

3930 

9780   

(2000-11000)

2460  

(910-3050)

25+25+35+35 

1720 

1720 

2340 

2340 

8120     

(1800-9400)

2460     

(710-3350)

2065 

2065 

2800 

2800 

9730   

(2000-11000)

2440  

(910-3050)

25+25+35+50 

1520 

1520 

2040 

3020 

8100     

(1800-9400)

2480     

(710-3350)

1800 

1800 

2430 

3750 

9780   

(2000-11000)

2460  

(910-3050)

25+35+35+35 

1620 

2160 

2160 

2160 

8110     

(1800-9400)

2480     

(710-3350)

1930 

2600 

2600 

2600 

9730   

(2000-11000)

2450  

(910-3050)

35+35+35+35 

2030 

2030 

2030 

2030 

8120     

(1800-9400)

2490     

(710-3350)

2425 

2425 

2425 

2425 

9700   

(2000-11000)

2470  

(910-3050)

 

 

 

 

 

5.2    Indoor Units Data 

5.2.1    Indoor Units Capacity For 2.5KW 

 

Capacity 

Model 

CMVS-25V3A-A38A 
CMVS-25V3A-A38B 
CMVS-25V3A-A48A 
CMVS-25V3A-A69A 
CMVS-25V3A-A46A 
CMV-V25G3A/A67 
CMV-V25G3A/A78 
CMV-V25G3A/A27 

2.5KW 

CMV-V25G3A/A77 

 

background image

 

28                         SERVICE MANUAL FOR CMV

 

 

5.2.1.1 

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C] 

OUTDOOR 

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA 

22/15 

24/17 

27/19 

29/21 

32/23 

 

TC 

80 - 110 % of nominal 

-10 - 20 

SC 

80 - 105 % of nominal 

(protection range)

PI 

25 - 50 % of nominal 

TC  2.42 2.57 2.73 2.89 3.05 

25 

SC  1.72 1.75 1.79 1.82 1.86 

 

PI  0.58 0.59 0.60 0.61 0.62 

 

TC  2.30 2.46 2.62 2.77 2.93 

30 

SC  1.67 1.71 1.74 1.78 1.81 

 

PI  0.65 0.66 0.67 0.68 0.69 

 

TC  2.18 2.34 2.50 2.66 2.82 

35 

SC  1.63 1.66 1.70 1.74 1.77 

 

PI  0.71 0.72 0.74 0.75 0.76 

 

TC  2.07 2.23 2.38 2.54 2.70 

40 

SC  1.59 1.62 1.66 1.69 1.73 

 

PI  0.78 0.79 0.80 0.81 0.82 

 

TC  1.93 2.09 2.24 2.40 2.56 

46 

SC  1.53 1.57 1.60 1.64 1.67 

 

PI  0.86 0.87 0.88 0.89 0.91 

 

L E G E N D  

TC – Total Cooling Capacity, kW       
SC – Sensible Capacity, Kw         
PI – Power Input, kW 
WB – Wet Bulb Temp., (

o

C)    

DB – Dry Bulb Temp., (

o

C)         

ID – Indoor 

 

OD – Outdoor 

 

 

 

 

 

 

 

 

 

 

 

 

background image

 

29                         SERVICE MANUAL FOR CMV

 

 

5.2.1.2 

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

ID COIL ENTERING AIR DB TEMPERATURE [

0

C] 

OD COIL 

ENTERING 

AIR DB/WB 

TEM PERATU RE 

[

0

C] 

DATA 15 

20 

25 

-15/-16 

TC 

1.92 1.77 1.65 

 PI  0.49 

0.54 

0.59 

-10/-12 

TC 2.13 

1.98 

1.86 

 PI 

0.59  0.64  0.70 

              -7/-8 

TC 2.28 

2.16 

2.01 

 PI 

0.67 

0.72 

0.77 

                -1/-2 

TC 2.37 

2.25 

2.10 

 PI 

0.71  0.75  0.80 

2/1 

TC 

2.43 2.28 2.16 

 PI 

0.73 

0.78 

0.83 

7/6 

TC 

3.12 3.00 2.88 

 PI 

0.77  0.82  0.87 

              10/9 

TC 

3.30 3.18 3.03 

 PI 

0.82 

0.87 

0.92 

       15/12 

TC 

3.48 3.36 3.21 

 PI 

0.86 

0.90 

0.96 

              15-24 

TC 

85 - 105 % of nominal 

(Protection Range) 

PI 

80 - 120 % of nominal 

 

 

 

 

5.2.1.3 Capacity 

Correction 

Factors 

Cooling Capacity Ratio Vs. Outdoor Temperature 

                       

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

 

 

 

background image

 

30                         SERVICE MANUAL FOR CMV

 

 

Heating Capacity Ratio Vs. Outdoor Temperature 

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

 

 

5.2.2  Indoor Units Capacity For 3.5KW 

 

5.2.2 Indoor 

Units 

Capac

ity For 

3.5KW 

Capacity 

Model 

CMVS-35V3A-A38A 
CMVS-35V3A-A38B 
CMVS-35V3A-A48A 
CMVS-35V3A-A69A 
CMVS-35V3A-A46A 
CMV-V35G3A/A67 
CMV-V35G3A/A78 
CMV-V35G3A/A27 

3.5KW 

CMV-V35G3A/A77 

 

 

 

 

 

 

 

background image

 

31                         SERVICE MANUAL FOR CMV

 

5.2.2.1 

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C] 

OUTDOOR 

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA 

22/15 

24/17 

27/19 

29/21 

32/23 

 

TC 

80 - 110 % of nominal 

-10 - 20 

SC 

80 - 105 % of nominal 

(protection range)

PI 

25 - 50 % of nominal 

TC 

3.40

3.61

3.82

4.06 

4.27

25 

SC 

3.03 

3.09 

3.15 

3.21 

3.27 

 PI 

0.86

0.87

0.89

0.90 

0.93

 TC 

3.22 

3.43 

3.68 

3.89 

4.10 

30 

SC 

2.94

3.00

3.09

3.15 

3.21

 PI 

0.96 

0.97 

0.99 

1.00 

1.02 

 TC 

3.05 

3.29 

3.50 

3.71 

3.96 

35 

SC 

2.88 

2.94 

3.00 

3.06 

3.12 

 PI 

1.06 

1.08 

1.09 

1.11 

1.12 

 TC 

2.91 

3.12 

3.33 

3.57 

3.78 

40 

SC 

2.79 

2.85 

2.91 

3.00 

3.06 

 PI 

1.16 

1.18 

1.19 

1.21 

1.22 

 TC 

2.70

2.91

3.15

3.36 

3.57

46 

SC 

2.70 

2.76 

2.82 

2.88 

2.97 

 PI 

1.28 

1.30 

1.31 

1.33 

1.34 

 

 

5.2.2.2 

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

ID COIL ENTERING AIR DB TEMPERATURE [

0

C] 

OD COIL 

ENTERING 

AIR DB/WB 

TEM PERATU RE 

[

0

C] 

DATA 15 

20 

25 

-15/-16 

TC 

2.56 

2.36 

2.20 

 PI 

0.67 

0.73 

0.80 

-10/-12 

TC 

2.84 

2.64 

2.48 

 PI 

0.80 

0.87 

0.94 

              -7/-8 

TC 

3.04 

2.88 

2.68 

 PI 

0.91 

0.98 

1.04 

                -1/-2 

TC 

3.16 

3.00 

2.80 

 PI 

0.95 

1.02 

1.09 

2/1 

TC 

3.24 

3.04 

2.88 

 PI 

0.99 

1.05 

1.12 

7/6 

TC 

4.16 

4.00 

3.84 

 PI 

1.04 

1.11 

1.18 

              10/9 

TC 

4.40 

4.24 

4.04 

 PI 

1.11 

1.18 

1.24 

       15/12 

TC 

4.64 

4.48 

4.28 

 PI 

1.17 

1.23 

1.30 

              1524 

TC 

85 - 105 % of nominal 

(Protection Range) 

PI 

80 - 120 % of nominal 

 

background image

 

32                         SERVICE MANUAL FOR CMV

 

 

5.2.2.3 Capacity 

Correction 

Factors 

Cooling Capacity Ratio Vs. Outdoor Temperature 

                       

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

 

 

Heating Capacity Ratio Vs. Outdoor Temperature 

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

 

 

5.2.3    Indoor Units Capacity For 5.0KW 

Capacity 

Model 

CMV-V50G3A/H38A 

CMVS-50V3A-N46A 

CMVS-50V3A-N17A 

CMV-V50G3A/H27 

CMV-V50G3A/H69 

CMV-V50G3A/H48 

5.0KW 

CMV-V50G3A/H77 

background image

 

33                         SERVICE MANUAL FOR CMV

 

 

5.2.3.1    Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at high 

speed 

 

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C] 

OUTDOOR 

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA 

22/15 

24/17 

27/19 

29/21 

32/23 

 

TC 

80 - 110 % of nominal 

-10 - 20 

SC 

80 - 105 % of nominal 

(protection range)

PI 

25 - 50 % of nominal 

TC 

4.85

5.15

5.45

5.80 

6.10

25 

SC 

4.55 

4.64 

4.73 

4.82 

4.91 

 PI 

1.23

1.25

1.28

1.29 

1.33

 TC 

4.60 

4.90 

5.25 

5.55 

5.85 

30 

SC 

4.41

4.50

4.64

4.73 

4.82

 PI 

1.37 

1.39 

1.42 

1.44 

1.47 

 TC 

4.35 

4.70 

5.00 

5.30 

5.65 

35 

SC 

4.32 

4.41 

4.50 

4.59 

4.68 

 PI 

1.51 

1.54 

1.56 

1.59 

1.61 

 TC 

4.15 

4.45 

4.75 

5.10 

5.40 

40 

SC 

4.19 

4.28 

4.37 

4.50 

4.59 

 PI 

1.65 

1.68 

1.70 

1.73 

1.75 

 TC 

3.85

4.15

4.50

4.80 

5.10

46 

SC 

4.05 

4.14 

4.23 

4.32 

4.46 

 PI 

1.83 

1.86 

1.87 

1.90 

1.92 

 

5.2.3.2   Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

ID COIL ENTERING AIR DB TEMPERATURE [

0

C] 

OD COIL 

ENTERING 

AIR DB/WB 

TEM PERATU RE 

[

0

C] 

DATA 15 

20 

25 

-15/-16 

TC 

3.71 

3.42 

3.19 

 PI 

0.97 

1.06 

1.16 

-10/-12 

TC 

4.12 

3.83 

3.60 

 PI 

1.16 

1.26 

1.37 

              -7/-8 

TC 

4.41 

4.18 

3.89 

 PI 

1.32 

1.42 

1.51 

                -1/-2 

TC 

4.58 

4.35 

4.06 

 PI 

1.38 

1.48 

1.58 

2/1 

TC 

4.70 

4.41 

4.18 

 PI 

1.43 

1.53 

1.63 

7/6 

TC 

6.03 

5.80 

5.57 

 PI 

1.51 

1.61 

1.71 

              10/9 

TC 

6.38 

6.15 

5.86 

 PI 

1.61 

1.71 

1.80 

       15/12 

TC 

6.73 

6.50 

6.21 

 PI 

1.69 

1.79 

1.88 

              15-24 

TC 

85 - 105 % of nominal 

(Protection Range) 

PI 

80 - 120 % of nominal 

 

background image

 

34                         SERVICE MANUAL FOR CMV

 

5.2.3.3 Capacity 

Correction 

Factors 

 

Cooling Capacity Ratio Vs. Outdoor Temperature 

                       

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

 

 

 

 

Heating Capacity Ratio Vs. Outdoor Temperature 

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

 

 

 

 

 

5.2.4 

Indoor Units Capacity For 2.0KW 

Capacity 

Model 

2.0KW 

CMV-V20G3A/G38A 

background image

 

35                         SERVICE MANUAL FOR CMV

 

5.2.4.1 

Cooling Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

INDOOR ENTERING AIR DB/WB TEMPERATURE [

0

C] 

OUTDOOR 

ENTERING AIR DB

TEMPERATURE

[

0

C] DATA 

22/15 

24/17 

27/19 

29/21 

32/23 

TC 

80 - 110 % of nominal 

SC 

80 - 105 % of nominal 

-10 - 20 

(protection range)

PI 

25 - 50 % of nominal 

TC 

1.94 

2.06 

2.18 

2.32   

2.44 

SC 

1.72   

1.75   

1.79   

1.82   

1.85   

25 

PI 

0.49 

0.50 

0.51 

0.51   

0.53 

TC 

1.84   

1.96   

2.10   

2.22   

2.34   

SC 

1.67 

1.70 

1.75 

1.79   

1.82 

30 

PI 

0.55   

0.55   

0.56   

0.57   

0.58   

TC 

1.74   

1.88   

2.00   

2.12   

2.26   

SC 

1.63   

1.67   

1.70   

1.73   

1.77   

35 

PI 

0.60   

0.61   

0.62   

0.63   

0.64   

TC 

1.66   

1.78   

1.90   

2.04   

2.16   

SC 

1.58   

1.62   

1.65   

1.70   

1.73   

40 

PI 

0.66   

0.67   

0.68   

0.69   

0.69   

TC 

1.54 

1.66 

1.80 

1.92   

2.04 

SC 

1.53   

1.56   

1.60   

1.63   

1.68   

46 

PI 

0.73   

0.74   

0.74   

0.76   

0.76   

 

 

5.2.4.2 

Heating Capacity (KW)---Run Model (Unit A,B,C or D),230V,Indoor fan at 

high speed 

 

ID COIL ENTERING AIR DB TEMPERATURE [

0

C] 

OD COIL 

ENTERING 

AIR DB/WB 

TEM PERATU RE 

[

0

C] 

DATA 15 

20 

25 

-15/-16 

TC 

1.54   

1.42   

1.32   

 PI 

0.40   

0.44   

0.48   

-10/-12 

TC 

1.70   

1.58   

1.49   

 PI 

0.48   

0.52   

0.57   

              -7/-8 

TC 

1.82   

1.73   

1.61   

 PI 

0.55   

0.59   

0.63   

                -1/-2 

TC 

1.90   

1.80   

1.68   

 PI 

0.58   

0.62   

0.66   

2/1 

TC 

1.94   

1.82   

1.73   

 PI 

0.60   

0.64   

0.68   

7/6 

TC 

2.50   

2.40   

2.30   

 PI 

0.63   

0.67   

0.71   

              10/9 

TC 

2.64   

2.54   

2.42   

 PI 

0.67   

0.71   

0.75   

       15/12 

TC 

2.78   

2.69   

2.57   

 PI 

0.70   

0.74   

0.78   

              1524 

TC 

85 - 105 % of nominal 

(Protection Range) 

PI 

80 - 120 % of nominal 

 

background image

 

36                         SERVICE MANUAL FOR CMV

 

5.2.4.3 Capacity 

Correction 

Factors 

 

Cooling Capacity Ratio Vs. Outdoor Temperature 

                       

Cooling Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

25

30

35

40

45

Outdoor Temperature (deg C)

Capacity Ratio

32/23
29/27
27/19
24/17
22/15

 

 

 

 

 

 

Heating Capacity Ratio Vs. Outdoor Temperature 

Heating Capacity Correction Factor

0

0.2

0.4

0.6

0.8

1

1.2

1.4

-15

-10

-5

0

5

10

15

20

Outdoor Temperature (deg C)

Capacity Ratio

15
20
25

 

 

 

 

 

 

background image

 

37                         SERVICE MANUAL FOR CMV

 

5.3  Capacity Correction Factor Due to Tubing Length (One Way)

 

5.3.1  Indoor units Model 

CMVS-25V3A-A38A 

CMVS-35V3A-A38A 

CMV-V20G3A/G38A 

CMV-V50G3A/H38A 

CMVS-25V3A-A38B 

CMVS-35V3A-A38B 

CMVS-25V3A-A48A 

CMVS-35V3A-A48A 

CMVS-25V3A-A69A 

CMVS-35V3A-A69A 

CMVS-25V3A-A46A 

CMVS-35V3A-A46A 

CMV-V25G3A/A27 

CMV-V35G3A/A27 

CMV-V25G3A/A77 

CMV-V35G3A/A77 

CMV-V25G3A/M85 

CMV-V35G3A/M85 

CMVS-50V3A-N46A 

CMVS-50V3A-N17A 

CMV-V25G3A/A67 

CMV-V35G3A/A67 

CMV-V25G3A/A78 

CMV-V35G3A/A78 

CMV-V50G3A/H27 

CMV-V50G3A/H69 

CMV-V50G3A/H48 

CMV-V50G3A/H77 

 

5.3.1.1   Cooling 

 

 

5.3.1.2   Heating 

 

 

background image

 

38                         SERVICE MANUAL FOR CMV

 

 

6.  Pressure Curve 

                                                                                                   

6.1          Model 

CMV-50V3A-E2 

CMV-71V3A-T  CMV-V80WC3AQ

CMV-V40H13AD

 

 

6.1.1   Cooling--------------Test Model 

 

 

6.1.2     Heating-----------Test Model 

 

 

 

background image

 

39                         SERVICE MANUAL FOR CMV

 

7 .   E L E C T R I C A L  

D A T A  

Model  

CMV-50V3A-E2

 

Power Supply 

1 PH, 220-240 VAC, 50Hz 

Connected to 

Outdoor 

Maximum Current 

11 A 

Inrush Current 

  35A 

Starting Current 

  1A 

Circuit breaker 

  20A 

Power supply wiring - No. x cross section 

1 X 3 X 2.5 mm

Interconnecting cable - No. x cross section 

2 X 4 X 1 mm

2

 

 

Model  

CMV-71V3A-T

 

Power Supply 

1 PH, 220-240 VAC, 50Hz 

Connected to 

Outdoor 

Maximum Current 

  16A 

Inrush Current 

  35A 

Starting Current 

  2A 

Circuit breaker 

  20A 

Power supply wiring - No. x cross section 

1 X 3 X 2.5 mm

Interconnecting cable - No. x cross section 

3X 4 X 1 mm

2

 

 

Model  

CMV-V80WC3AQ

 

Power Supply 

1 PH, 220-240 VAC, 50Hz 

Connected to 

Outdoor 

Maximum Current 

  16A 

Inrush Current 

  35A 

Starting Current 

  2A 

Circuit breaker 

  20A 

Power supply wiring - No. x cross section 

1 X 3 X 2.5 mm

Interconnecting cable - No. x cross section 

3X 4 X 1 mm

2

 

 

Model  

CMV-V40H13AD

 

Power Supply 

1 PH, 220-240 VAC, 50Hz 

Connected to 

Outdoor 

Maximum Current 

8 A 

Inrush Current 

  35A 

Starting Current 

  1A 

Circuit breaker 

  20A 

Power supply wiring - No. x cross section 

1 X 3 X1.5 mm

Interconnecting cable - No. x cross section 

2 X 4 X 1 mm

2

 

 
Note: 

Inrush current is the current when power is up. (charging the DC capacitors at outdoor unit 
controller). 
Starting current is the current when starting the compressor 
NOTE 

Power wiring cord should comply with local lows and electrical regulations 
requirements. 

 

background image

 

40                         SERVICE MANUAL FOR CMV

 

8 .   W I R I N G  

D I A G R A M S  

8 . 1   C M V - 5 0 V 3 A - E 2  

 

      C M V - V 4 0 H 1 3 A D  

CN13

CN12

CN1

CN6

SW

   

SC
N

2

.5

-2

P

C

N

15  

 V
H

3

.9

6

-4P

CN7

CN8

WH
RD
RD

COM

953-1A-12DB

NO

CN5

P

U

V

W

N

BR

BK
BL

 CN9

RD

BR
BK

RD

OR

YL

BK

YL

OR

RD

BR

RD

WH

IA

1

IA

2

IA

3

IA

4

CN1

BK

WH

To compressor 

temperature protector

RD

WH

EARTH

AC-N

AC-L

WB1021B8004

MBZ102B120

3

VB109B3118

BL

RD

AC-L

AC-N

L

2

N

WH
RD

ZB102B9108

COMPRESSOR

BL

RD

N

N

A

S

A

L

B

N

B

S

B

L

A

BR

BL

BK

HI

N

ME

D
LOW

F

o

u

r-p
o

sitio
n

Va
lv

e

Expansion Valve:B  Expansion Valve:A  

1

2

1

5

L

1

p

AC-N

AC-L

AC-L1

AC-N1

AC-N1

AC-N

AC-L

BK

BK

BK

WH

CN10

L

3
2

BK

WH

1

BR

BR
BK

WH

P

N

BK

                   UF-1330A

Y/G

BL

RD

RD

BL

HT225-15-L8-H2

CN1

SB
SA

AC-L

AC-N

reactor

AC-L1

T3

 

 

T1

 

 

T2

 

 

T4

 

 

simulant quantity input:

IA4: inspiration temperature

IA3:condensator midpiont 

     temperature

IA2:outside temperature

IA1:exhaust temperature

others:

Y/G

Y/G

WH

GR

RD

RD

GR

ZB102B9108:PFC board
WB1021B8004:filter board

VB109B3118:IPM board

MBZ102B1203:mainboard

HT225-15-L8-H2:filter 

 WIRE COLOUR:
 BL(BLUE),BK(BLACK),
 BR(BROWN),RD(RED),
 GR(GREEN),YL(YELLOW),
 Y/G(YELLOW/GREEN),
 WH(WHITE),OR(ORANGE)

YL

BK

BL

WH

 

8 . 2   C M V - V 8 0 W C 3 A  

W i r i n g   D i a g r a m  

 

 

 

 

 

 

background image

 

41                         SERVICE MANUAL FOR CMV

 

8 . 3   C M V - 7 1 V 3 A - T  

W i r i n g   D i a g r a m  

 
8 . 4     C M V - 5 0 V 3 A - E 2                     C M V - V 4 0 H 1 3 A D        

I n d o o r - O u t d o o r   W i r i n g   D i a g r a m  

 

background image

 

42                         SERVICE MANUAL FOR CMV

 

 
8 . 5       C M V - 7 1 V 3 A - T  I n d o o r - O u t d o o r   W i r i n g   D i a g r a m  

 

8 . 6       C M V - V 8 0 W C 3 A Q  I n d o o r - O u t d o o r   W i r i n g   D i a g r a m  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

background image

 

43                         SERVICE MANUAL FOR CMV

 

9. REFRIGERATION 

DIAGRAMS

 

 
9 . 1     C M V - 5 0 V 3 A - E 2     R e f r i g e r a t i o n  D i a g r a m  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
9 . 2     C M V - 7 1 V 3 A - T  R e f r i g e r a t i o n  D i a g r a m  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

background image

 

44                         SERVICE MANUAL FOR CMV

 

9 . 3     C M V - V 8 0 W C 3 A Q     R e f r i g e r a t i o n   D i a g r a m  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
9 . 4     C M V - V 4 0 H 1 3 A D     R e f r i g e r a t i o n   D i a g r a m  

 

background image

 

45                         SERVICE MANUAL FOR CMV

 

1 0 .   T U B I N G   C O N N E C T I O N S  

 

 
 
 
 
 
 
                                                     
 
 
 
 
 
 
                                                           

 

 
 
 
 
 
 
 
 
 
 
 

When the outdoor unit is installed above the indoor unit an oil trap is required every 5m along the suction line at 
the lowest point of the riser. Incase the indoor unit is installed above the outdoor, no trap is required 
 
 
 
 
 
 
 
 
 
 
 
 
 

T U B E   ( I n c h )  

 

 

 

 

 

T O R Q U E   ( N m )  

¼ ”   ~ ”   ½ ”   ~ ”  ¾ ”  

F l a r e   N u t s  

11-13

40-45

60-65 70-75

80-85

V a l v e   C a p  

13-20

13-20

18-25 18-25

40-50

Service Port Cap 

11-13 11-13 11-13 11-13 11-13

1. 

Valve Protection Cap-end 

2. 

Refrigerant Valve Port (use Allen wrench to open/close) 

3. 

Valve Protection Cap 

4. Refrigerant 

Valve 

5. 

Service Port Cap 

6. Flare 

Nut 

7. 

Unit Back Side 

8. Copper 

Tube 

background image

 

46                         SERVICE MANUAL FOR CMV

 

1 1 .   C O N T R O L   S Y S T E M  

Function of Inverter indoor unit 

 

一、summary

 

1.  This control is use for DC Multi-Spilt air conditioners. 
2.  Power of indoor unit supply is 220-240V/50Hz, voltage range is 170V~270V. 
3.  Control precision of indoor temperature is ±1℃.  
4.  Indoor fan motor is PG motor. 
5.  Control accord with : 

  GB5956-91《safe requirement of air conditioner》 
  GB7725-2004《air conditioner》;GB3797-87《control equipment of electrical 

equipment》 

  Vibrancy test:frequency 50Hz,acceleration 2.5g 
  PCB ought to accord with GB4588.1 and GB4588.2 
  Electromagnetism compatibility ought to accord with relate standard of nation. 

二.Base parameter 

1.  Use condition:ambient temperature -15℃~85℃, relative humidity =30-95%. 
2.  Receive distance of remote:<10m 
3.  Angle of remote:<120 degree 
4.  Control precision of temperature: ±1℃ 
5.  Speed precision of indoor fan motor: ±10RPM 
6.  Time precision: <0.1% 

三.Major function of control 

1.  Remote 

  Turn on/off 
  Mode select  

 auto 
 cooling 
 dehumidify 
 heating 

  

 ventilation 

  Indoor fan speed select    

 manual mode: high, middle, low speed 
 auto mode: accord difference of indoor room temp. and set temp. automatic select. 

  Temperature setting 

 Cooling: 16℃――32℃, default is 25℃ 
 Heating : 16℃――32℃, default is 25℃ 
 Dehumidify: default is 25℃ and it can’t adjust. 
 Auto: default is 25℃ and it can’t adjust. 
 Ventilation: 16℃――32℃, default is 25℃ 

  Sleeping 

It can set or cancel 24HR sleep . 

  Timer on or timer off 

 Timer can set 24HR on or off. 

background image

 

47                         SERVICE MANUAL FOR CMV

 

  Air flower control. 
  Turbo running 
  Hold key 

2.  Main PCB board 

  five running modes 

Auto, cooling, heating,  dehumidify,  ventilation. 

 

Timer function 

  Indoor temperature detect. 
  Indoor coil temperature detect. 

  Indoor fan speed control  

cooling: turbo/high speed/middle speed/low speed/ lower speed 
heating: turbo/high speed/middle speed/low speed/ lower speed 

  Indicate lamp 

 green—running indicate 
 yellow—timer indicate 
 red—turbo running  
 green—economic running 

 Indoor temperature control 
 Coil pipe of indoor unit overheat protection 
 Coil pipe of indoor unit anti frost protection 
 Sleep  
 Swing 
 Anti cold air in heating mode 
 Indoor fan motor protection 

 

Fault display 

PG motor speed: 
5.0KW: 

mode 

higher

high 

middle

low 

lower 

Cooling 

speed 

1350 

1250 

950 

850 

750 

Heating 

speed 

1350 

1250 

950 

850 

750 

 
3.5KW: 

mode 

higher

high 

middle

low 

lower 

Cooling 

speed 

1350 

1250 

950 

850 

750 

Heating 

speed 

1350 

1250 

950 

850 

750 

 

2.5KW 

mode 

higher

high 

middle

low 

lower 

Cooling 

speed 

1250 

1150 

950 

850 

750 

Heating 

speed 

1250 

1150 

950 

850 

750 

background image

 

48                         SERVICE MANUAL FOR CMV

 

2.0KW: 

mode 

higher

high 

middle

low 

lower 

Cooling 

speed 

1250 

1150 

950 

850 

750 

Heating 

speed 

1250 

1150 

950 

850 

750 

 
 
 
四、operating mode 

Air conditioner have four operating mode: auto, cooling, dehumidify, heating. 
1.Cooling(ΔT=Troom temp.-Tset temp.) 

  range of set temp. 16℃~32℃; 
  compressor running as below figure: 

          

compressor 

on 

                       CONT 5 MIN 
                  off 

-1ºC     +1ºC   ΔT

 

  It require outdoor unit to reduce power if indoor room temp. continuous less than 

set temp. for 5 minutes. 

  Air blow function:indoor blower fan continuous running 20 seconds at low speed 

after air conditioner turn off in cooling mode. if the flap is swing, shutdown the 
flap after turn off indoor blower fan. 

  Indoor blower fan can select one of four speed. 

  Fan speed is determined by the difference of room temp. and set temp. in auto wind. 

             

speed 

                            high 
                              middle 

low

 

1ºC   3ºC   5ºC   ΔT 

 

It have anti freeze protection of indoor coil ,fan motor fault protection, sensor 

fault protection, unit abnormal protection in cooling mode. 

2.Dehumidify:(ΔT=Troom temp.-Tset temp.) 

  range of set temp.: default is 25℃ and it can’t change.  
  The indoor blower fan is running at low speed for thirty seconds after air 

conditioner shutdown in dehumidify mode.  

  The indoor blower fan is running at low speed and it can’t change. 
  Air conditioner haven’t turbo and economic function in dehumidify mode.  

 

Flap position: flap at 85 degree position and it can’t change.  

  It require indoor unit to reduce power if indoor room temp. continuous less than 

or equal to 15 degree for 5 minutes, when room temp. is more than or equal to 17 
degree, it add the power of indoor unit.  

3.Heating(ΔT=Troom temp.-Tset temp.) 

  Range of set temp. 16℃~32℃; 
  Compressor running as below figure. 

 
 
 

background image

 

49                         SERVICE MANUAL FOR CMV

 

 
        

compressor 

on 

                     CONT 5 MIN 
                 off 
                           

   

-4℃ 

    

-2℃

 

  ΔT

 

  It require outdoor unit to reduce power if indoor room temp. continuous more than 

set temp. for 5 minutes. 

  Indoor blower fan continuous running for 30 seconds at current speed after indoor 

unit reduce power. 

  Indoor blower fan can select one of four speed. 

  Fan speed is determined by the difference of room temp. and set temp. in auto 

wind.(but anti cold wind is prior) 

             

speed 

                high 
                middle 

low 

0ºC  2ºC   3ºC  5ºC       ΔT

 

  Anti cold wind: 

 When air conditioner first power on or change mode, indoor blower fan didn’t running. When 

the coil pipe temp. of    indoor unit is more than 30℃,start turnning on indoor blower 
fan(lower speed).if the coil pipe temp. of indoor unit drop to less than or equal 
to 25℃,it shutdown indoor blower fan. 

 Heat wind control: 

      If coil pipe temp. of indoor unit is more than or equal to 32℃, indoor blower fan is 

running at set speed. 

      If coil pipe temp. of indoor unit is less than 32℃, indoor blower fan is running as below 

figure. 

                     

speed 

             set speed 
                lower 

 turn off 

                      25℃   30℃     32℃   coil pipe temp.  

Note:①When Tp≤30℃,flap is open at 85°and is running at lower speed, when Tp

≥32℃, it is running at set speed and flap revert to prior state.  

②If Tp≤25℃,turn off indoor blower fan.

 

  Defrost control 

Indoor blower fan turn off when it enter defrost.  

  Clear quantity of heat 

 Turn off air conditioner in heating mode, if the coil pipe temp. of indoor unit 

is more than 40℃, indoor blower fan is running at low speed. If the coil pipe 
temp. of indoor unit is less than or equal to 40℃ or turn off air conditioner 
over 2 minutes, It shutdown indoor blower fan. 

4. Auto mode 

  set temp. is 25℃ and it can’t change; 

 

Press emergency key in waiting state or select auto mode by remote, air 

conditioner enter auto mode and set temp. is 25℃. 

 

Indoor blower fan is running for 20 seconds at lower speed after select auto 

background image

 

50                         SERVICE MANUAL FOR CMV

 

mode, the running lamp is light, it select correspond running mode accord to room 

temp.: 

room temp. >26℃, select cooling mode. 
room temp. <21℃, select heating mode. 
21ºC≤room temp.≤26ºC,select ventilation mode. 

When the running mode has confirmed, it can’t change, if it reenter auto mode, 
it select running mode again accord to room temp.. 

  When the mode of auto select is clash with other indoor unit running mode: 

  If it auto select is cooling mode and other indoor unit is running heating mode, then it select 

ventilation mode. 

  If it auto select is heating mode, but other indoor unit is running cooling mode, display error of 

mode clash. 

  if it select is ventilation mode, then it running is ventilation. 

5.Ventilation 

   

 1) Range of set temp.:16℃-32℃. 

   2) Indoor blower fan is operate same as cooling mode. 
   3) Flap is  operate same as cooling mode. 

4) Indoor unit no power require in ventilation mode. 

 
6 Timer and sleep 

  timer 

  Remote can set 1-24 hours timer on or timer off. 
  Air conditioner is running . 

If set timer off,    air conditioner is continuous running and display timer time, when timer time is 
end, it shutdown air conditioner.   

  air conditioner is shutdown . 

If set timer on,    air conditioner at waiting state, it display timer time. when timer time is end, it 
turn on air conditioner.   

  when it set timer , the timer lamp is light and display set temp.   

  sleep 

If set sleep, the sleep lamp is light, set temp. and fan speed can be adjust.  
Timer and sleep can set together, which time is end then perform this function. 

7.  Air flow control 

Define:flap full open angle is 0°, and full close angle is 125°。 

 

 

  Power on, flap run to full close position. 

Full open 

Full close 

Fixed 

background image

 

51                         SERVICE MANUAL FOR CMV

 

  Turn off    air conditioner, flap run to full close position. 
  Turn on air conditioner, flap first run to full open position, then run to correspond position. 
  Fixed wind: 

  If turn on air conditioner and set fixed wind at first power on, flap first run to full open 

position then stop at    40°position. 

  If change to fixed wind from swing wind or natural wind, the flap stop at current position 

and store the position. 

  Swing wind: 

  Flap start position is 20°. 
  Flap is running between 20°and 85°.     

  Natural wind is swing two cycle and stop 15 seconds, flap is stop at current 

position at that moment. 

  Flap stop at 85°at anti cold wind or defrost procedure in heating mode. 
  Flap stop at 85°in first 20 seconds of auto mode.  
  Flap is drive by step motor. 

8. Turbo function 

Turbo is use in cooling /heating/ventilation mode, the indoor blower fan is running 

at super speed.  

(1) enter condition: press turbo key of remote. 

(2)end condition:   

①  running time more than or equal to 15 minutes. 
②  press turbo key of    remote again. 

(3) all restrict and protect condition are active in turbo running. 
(4) return to prior state after end turbo running. 

五、Protection 

1. Prevent frost of indoor coil pipe (cooling and dehumidify mode)                         

  When the temp. of middle coil pipe is less than or equal to 0℃, indoor blower 

fan is running at high speed, if the temp. less than or equal to -1℃ for 5 minutes, 
it turn off compressor, when the temp. more than or equal to 7℃, it exit 
protection.  

2. Overheat of indoor coil pipe(heating mode) 

 When the temp. of middle coil pipe more than or equal to 57℃, indoor blower fan 

is running at high speed, if the temp. more than or equal to 65℃ , it turn off 
outdoor unit, when the temp. less than or equal to 54℃, it exit protection.  

3. Indoor fan motor fault(only PG motor) 

  If no feedback signal continuous 30 seconds during PG motor running, it turn off 

air conditioner and display fan motor error.  

4. Communicate fault 

 If it can’t receive correct signals after air conditioner has run for 60 seconds, 

it turn off air conditioner and display communicate error.  

5.Indoor sensor fault 
    When indoor sensor cut off or short, it shutdown air conditioner and display sensor 

error. 

6. When outdoor unit is fault, indoor unit only display fault. 

六、Other function   

Emergency key 

Press emergency key after power on, air conditioner select auto mode, auto fan speed, natural wind, 

it set temp. is 25℃. If press emergency key again, air conditioner is shutdown.  

background image

 

52                         SERVICE MANUAL FOR CMV

 

七、Sound indication   

1.  The buzzer will sound when air conditioner turn on , turn off, power on or receive remote signal. 

八、Display 

1.After turn on air conditioner, mode clash display 

d1 

and timer lamp flash (light 

one second, extinguish one second), defrost display 

dF

 , the running lamp flash (light 

one second, extinguish one second)indicate anti cold wind ,when air conditioner is  
normal running ,  the running lamp is light.  

2.Set timer or sleep , the yellow lamp is light.  
3.Outdoor unit and indoor unit fault display: 

  Fault display of indoor unit: 

fault 

display  

Communicate fault  

F1 

Fan motor fault  

F4 

Room temp. sensor fault  

F2 

Temp. sensor of coil pipe outlet fault 

F3 

Temp. sensor of coil pipe entrance 

fault  

F3 

Temp. sensor of coil pipe middle 

fault  

F3 

 

  Fault display of outdoor unit: 

fault  

display  

Transducer module protection  

P2 

Over current  

P3 

Discharge temperature of 

compressor overheat, ambient 

temperature overheat 

P4 

DC voltage of outdoor unit abnormal 

P7 

Leakage or reverse valve fault  

P8 

Outdoor sensor fault  

F6 

Compressor drive fault   

FC 

 

Function of Dual DC Inverter Type

 

. System Frame Drawing 

                        R

everse Valve(Current in cooling condition

) 

                                                                       

Condenser of Outdoor Unit 

           

                                                               

Temperature of the Middle of Outdoor Coils   

 

Temperature of Exhaust                                         

                                                                                                              Expansion Valve 1        Expansion Valve 2 

       

Temperature of suction

                                      M          M 

Compressor                     

    

Liquid Tank   

  

                              T11                      T12                    T13

 

                                                                     

Evaporator 1 of Indoor Unit 

                                                                                                       

Ambient Temperature of Indoor 1 

Ambient Temperature of Outdoor                              T21                      T22                    T23 
                                                                                                  Evaporator 2 of Indoor Unit 

 

                                                                                         

 Ambient Temperature of Indoor 2                 

Diagram 1 

background image

 

53                         SERVICE MANUAL FOR CMV

 

二.Major Performance Index 

a)  Voltage of Power Supply: AC220V ±15%; 
b)  Power of Controller: ≤15W; 
c)  Output of Three-phase Frequency Conversion: 

Wire Voltage: 70V∽180V; Power:  ≤5KW; Frequency: 10Hz∽120Hz; 

d)  Precision of Temperature Control:±1℃; 
e)  Applicable Environment: 

Temperature:-20∽55℃,Relative Humidity:  ≤90%RH (No dew); 

f)  Conservation Environment: 

Temperature:-25∽70℃,Relative Humidity:  ≤95%RH (No dew); 

g)  Executive Standard: GB/T7725-2004 & GB4706.32-2000. 

 
三.Input & Output of Outdoor Controller 

1. 

Outputs of one three-phase Frequency Conversion, two relays, one indicator led and one 

communication signal: 
1) Controlling the three-phase output of compressor   
2) Controlling the output of outdoor motor 
3) Controlling the output of 4-way valve   
4) Controlling the output of communication signals of indoor unit   
5) Controlling the output of expansion valve   
 

 

2.  Inputs of five analogue inputs (the temperature measuring points distributing as Diagram 1, all 

the analogues go through digital filter for disposal), and two switch signals and two 
communication signals: 

a)  Signal input of outdoor ambient temperature 
b)  Signal input of median temperature of outdoor coil   
c)  Signal input of discharge temperature of compressor 
d)  Signal input of suction temperature of compressor 
e)  Signal input of power supply voltage 
f)  over-heat protection signal of compressor 
g)  communication signal of indoor unit 1 
h)  communication signal of indoor unit 2 
i)  protection signal of outdoor IPM module 

 

. Operation in Cooling Mode 

Control of Expansion Valve in Cooling Mode 

1.  Reset of Expansion Valve 

In the first time  ,the expansion valves in all channels shall be shut down 600 steps, then the 

expansion valve corresponding to the indoor unit in normal communications with the outdoor unit 
shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode, 
until the turn-on the indoor unit. 

 

2.  Adjustment of Expansion Valve 

1)  Setting of Basic Step 

After the confirmation of the turn-on order of cooling mode, the expansion valve of the 
relevant indoor unit shall be set to the basic step and the other to zero step.       
 

2)  Adjustment of Expansion Valve according to the difference in temperature between the inlet 

and outlet of evaporator 

background image

 

54                         SERVICE MANUAL FOR CMV

 

During the first ten minutes of cooling mode, the expansion valve of the indoor unit at the 
request of cooling shall be set to the basic step. Ten minutes later, the expansion valve step and 
its adjust cycle shall be adjusted according to the difference in temperature between the inlet 
and outlet of evaporator. 

   

 

Control of compressor’s frequency: 

1.Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest 

frequency) 

2.Frequency decrease protection of compressor: frequency decrease protection is 

prior during frequency adjustment of compressor (Frequency decrease protection 
have: high temperature of compressor discharge, high temperature of outdoor coil 
pipe, high temperature of indoor coil pipe, low temperature of compressor  suction, 
over  current) 

 

Control of fan motor in cooling mode: 
1.The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on.; 
2.After compressor turn off, the fan motor of outdoor unit delay 30 seconds.   
3.  The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay 

after speed change. 

Speed table of outdoor fan motor 

 indoor unit 

capacity 

outdoor ambient 

<2hp 

2hp 

3hp 

cooling Speed 

grade 

T<19℃ 

low low 

 

middle 

19℃≤T<27℃ 

low middle high 

T≥27℃ 

middle high  high 

 
 
 
 
 
 

            compressor 

outdoor FM 

   

                     

  

20s         30s    30s 

figure 3 

Operation in Dehumidify Mode   

Dehumidify mode is same as cooling mode.  

Operation in heating Mode 

Adjustment of Expansion Valve: 
1.Reset of Expansion Valve   

In the first time,the expansion valves in two channels shall be shut down 600 steps, then the 

expansion valve corresponding to the indoor unit in normal communications with the outdoor unit 

background image

 

55                         SERVICE MANUAL FOR CMV

 

shall be opened to standby mode steps. If accomplished, the outdoor unit shall be on standby mode, 
until the turn-on the indoor unit. 
2.Adjustment of Expansion Valve 

1)  Setting of Basic Step 

After the confirmation of the turn-on order in heating mode, the expansion valve of the 
relevant indoor unit shall be set to the basic step.  

2)  Adjustment of Expansion Valve according to the difference in temperature between the inlet 

and outlet of evaporator 

During the first ten minutes of heating mode, the expansion valve of the indoor unit shall be 
set to the basic step and can’t adjust. Ten minutes later, the expansion valve step and its adjust 
cycle shall be adjusted according to the difference in temperature between the inlet and outlet 
of evaporator.       

Control of compressor’s frequency 

Range of compressor’s frequency:Fmin~Fmax (Fmin:the lowest frequency, Fmax:the highest 
frequency) 

Control of fan motor in heating mode:(figure 5) 

1.  The fan motor of outdoor unit is ahead run 20 seconds before compressor turn on. 
2.  After compressor turn off, the fan motor of outdoor unit delay 30 seconds. 
3.  The fan motor speed of outdoor unit as below table in normal running, it has 20 seconds delay 

after speed change.   

4.  The control of outdoor fan motor as figure 6 during defrost process.   

Speed table of outdoor fan motor 

 indoor unit 

capacity 

outdoor ambient 

<2hp 

≥2hp 

≥3hp 

heating Speed 

grade 

T≥20℃ 

low low 

middle 

12℃≤T<20℃ 

low middle high 

T<12℃ 

middle high  high 

 
Control of reverse valve
(figure 5) 

1.  The reverse valve is ahead run 20 seconds before compressor turn on.   
2.  After compressor turn off, the reverse valve delay 60 seconds shutdown.   
3.  The control of reverse valve as figure 6 during defrost process.   

 

              compressor 

outdoor FM 

   

          reverse valve 

  

20s         30s    30s 

figure 5 

七.Defrost of heating mode(figure 6) 

1.  Defrost start condition   

If outdoor ambient is more than or equal to 16℃,it can’t defrost. When the time of 
defrost interval is end , outdoor coil pipe temp. and outdoor ambient temp. 
continuous meet all conditions for 5 minutes, it enter defrost process: 

1)  If outdoor ambient temp. less than or equal to 0℃,when T

≤0.8T

+a℃(a is a adjust 

constant), it enter defrost process. 

background image

 

56                         SERVICE MANUAL FOR CMV

 

2)  If outdoor ambient temp. more than 0℃ and less than or equal to 15℃,when T

≤ 0.2 T

+a℃, it enter defrost process. 

3)  If outdoor temp. sensor is failure, when outdoor coil temp. T

≤+a℃, it enter defrost 

process. 

4)  If coil temp. sensor of outdoor unit is failure, when defrost interval time is end, it enter defrost, 

the time of defrost is four minutes. 

5)  During the first ten minutes of outdoor running in heating mode, the time is clear and it judge 

whether outdoor coil pipe temp. and outdoor ambient temp. satisfy defrost condition, if the 
frequency of compressor is 25HZ and satisfy defrost condition, then if enter defrost process. 
After end defrost process or over 10 minutes it return normal running.   

2.  Defrost end condition 

1)  T

≥b℃(b is a adjust constant)or defrost time more than or equal to c minutes

(c is a adjust constant),it exit defrost process.   

2)  When outdoor coil pipe sensor is failure, defrost time is four minutes, it exit defrost process 

after four minutes.   

3.  Interval time of defrost 

1)  Defrost interval time restriction: Max 120 minutes, Min 25 minutes.   
2)  The first frost interval time is 0 minute after heating. 
3)  The second defrost interval time is base on 60 minutes, it adjust according to below table. 
4)  Form second time, defrost interval time adjustment as below table. 

Interval time(Td) 

change 

Td <2 minutes 

Last interval time add 5 

minutes 

3 minutes≥Td≥2 

minutes 

Same as last interval time

≥4 minutes 

Last interval time reduce 5 

minutes 

 
 

4.  Time sequence of defrost process(figure 6). 

 

background image

 

57                         SERVICE MANUAL FOR CMV

 

八.Control of oil return circle   

1.  Oil return circle period 

When air conditioner has run for 10 minutes or accumulate time T

msro 

is end, it execute oil return 

circle once. 

2. 

When compressor is running to oil return circle, the indoor unit which have communication 

is return oil,          expand valve is open fully and compressor’s frequency increase more than 3/5 
of max frequency for 90 seconds, the expand valve of indoor unit which no communication is 
close.  

 

九.  Operation mode control of outdoor unit(dehumidify、cooling or heating) 

The indoor unit can require cooling mode and dehumidify mode together, but it can’t require cooling mode 

or dehumidify with heating mode together, the outdoor unit operate state is decided by the indoor unit which is 
applied first. 

 
十.Protect function: 

1.  Delay protection of compressor 

The compressor can’t run after it stop within 3 minutes. 

2.  Fault protection of module 

The air conditioner stop running immediately and display error code if the module 

is fault. 

3.  Protection of communicate fault 

The control of outdoor unit can connect with all indoor units, when it power on, 

it sent data to each indoor unit continuously, if it receive a correct data from 
correspond indoor unit, then the indoor unit is exist. when the control of outdoor 
unit didn’t receive communication data from indoor unit which is exist within 30 
seconds, it  will display communication  fault. If all communication channels are 
failure, air conditioner will shutdown and display fault code.  

 

4.  Leakage or reverse valve fault 

The air conditioner shutdown immediately when meet one of below conditions. 

1)  Heating: coil pipe temp. of outdoor unit can’t decrease 3 degree within setting 

time and coil pipe temp. of indoor unit can’t increase 3 degree all along.  

2)  Cooling: coil pipe temp. of outdoor unit can’t increase 3 degree within setting 

time and coil pipe temp. of indoor unit can’t decrease 3 degree all along.  

5.  High temp. protection of compressor discharge 

1)  The protection don’t effect if the temp. sensor of compressor discharge fault.   
2)  The air conditioner stop running immediately and display error code when the 

temp. of compressor discharge more than Tsd. 

3)  The compressor  decrease frequency until the temp. of compressor discharge less 

than 99℃    if the temp. of compressor discharge more than 95℃. The compressor resume 
normal frequency when the temp. of compressor discharge less than 90℃.   

6.  Temperature switch protection of compressor 

The air conditioner will shutdown immediately and display fault code if the temp. 
switch of compressor switch off. 

7.  High temp. protection of middle coil pipe of condenser 

1)  The protection don’t effect if the temp. sensor of middle coil pipe fault. 
2)  The compressor decrease frequency until the temp. of middle coil pipe less than 

58  ℃.if the temp. of middle coil pipe more than 57℃.. 

3)  It resume normal frequency when the temp. of middle coil pipe less than 56℃.. 

background image

 

58                         SERVICE MANUAL FOR CMV

 

8.  High temp. protection of indoor coil pipe 

1)  The compressor decrease frequency until the temp. of indoor coil pipe more than 

(Tsce-2) if the temp. of    indoor coil pipe less than (Tsce-2)in cooling mode. 

The compressor decrease frequency until the temp. of indoor coil pipe less than 
(Tsce+2) if the temp. of    indoor coil pipe more than (Tsce+2) in heating mode. 

2)  It resume normal frequency when the temp. of indoor coil pipe less than Tsce(cooling mode) 

or less than Tshe(heating mode). 

9.  Low temp. protection of compressor suction 

1)  The protection don’t effect if the temp. sensor of compressor suction fault or compressor 

don’t run or in heating mode.. 

2)  The compressor decrease frequency until the temp. of compress suction more than 

Tss if the temp. of    compressor suction less than Tss. It resume normal frequency when the 
temp. of compressor suction more than (Tss+2). 

10.Fault protection of outdoor sensor  

The air conditioner is running at the frequency of less than (3/5)*Fmax and display fault code 

if the temp. sensor of compressor discharge fault, or the temp. sensor of outdoor middle 
coil pipe fault, or the temp. sensor of compressor suction fault, or the temp. sensor 
of outdoor ambient fault.   

11.High temp. of ambient  

1)  The protection don’t effect if the temp. sensor of outdoor ambient fault. 
2)  The air conditioner stop running immediately and display error code if outdoor 

ambient temp. more than 55℃or less than -20℃. 

12. Over current protection of compressor 

1) The air conditioner stop running immediately and display error code when input 

current more than or equal to Imax. 

2) The compressor decrease 2Hz per 3 seconds until input current less than or equal 

to (Imax-13) when the input current more than  (Imax-13). 

2)The compressor decrease 1Hz per 3 seconds until input current less than or equal 

to (Imax-16) when the input current more than  (Imax-16). 

3) It resume normal frequency when the input current less than or equal to (Imax-20). 

13.DC voltage of wire protection 

1)  The air conditioner stop running and display DC voltage abnormal when it less 

than 260V. 

2)The compressor decrease frequency and display FA6 when DC voltage less than 285V. 
3) The air conditioner resume normal running when DC voltage more than 290V. 
 

十一、Outdoor unit fault of indoor unit display 
 

fault  

display  

Transducer module protection  

P2 

Over current  

P3 

Discharge temperature of 

compressor overheat, ambient 

temperature overheat 

P4 

DC voltage of outdoor unit abnormal

P7 

Leakage or reverse valve fault  

P8 

Outdoor sensor fault  

F6 

Compressor drive fault   

FC 

background image

 

59                         SERVICE MANUAL FOR CMV

 

 

12. TROUBLESHOOTING 

WARNING!!! 

When Power Up – the whole outdoor unit controller, including the wiring, is under HIGH 

VOLTAGE!!! 

Never open the Outdoor unit before turning off the Power!!! 

When turned off, the system is still charged (400V)!!! 

It takes about 3 Min. to discharge the system. 

Touching the controller before discharging may cause an electrical shock!!! 

For safe handling of the controller please refer to section 1.6 below. 

 

1.1 Air Conditioner Failures and Corrective Actions 

F1: 
1,Communicate wire cut off ,loose or wrong wiring---check wires   
2,Communication interfere---check wires connection with circuit diagram.(earth line must be 

wired)。 

 
F2: 
1,Temp. sensor of indoor room short or cut off.---change sensor 
 
F3: 
1,Temp. sensor of indoor coil pipe outlet short or cut off.---change sensor.   
2,Temp. sensor of indoor coil pipe entrance short or cut off.---change sensor. 
3,Temp. sensor of indoor coil pipe middle short or cut off.---change sensor.  
 
F4: 
1,PG motor fault.---change motor. PG.  
2,Fixed screw loose.---fix cross flow fan.   
3,Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.  
 
F6: 
1,Temp. sensor of discharge short or cut off.---change sensor.  
2,Temp. sensor of suction short or cut off.---change sensor.  
3,Temp. sensor of condenser middle  short or cut off.---change sensor.  
 
P2:(auto-restart) 
1,over current protection of inverter module. 
2,over voltage protection of inverter module. 
3,high temp. protection of inverter module. 
 
P3: 
1,over load (outdoor ambient temp. more high).  
2,Voltage over low. 

background image

 

60                         SERVICE MANUAL FOR CMV

 

 
P4: 
1: discharge temp. too high.---maybe leak refrigerant, add refrigerant.  
2:outdoor ambient temp. too high, if (T<-20,T>55), it will alarm. 
3:temp. switch of compressor cut off.。 
4:Communication interfere. (earth wire can’t with communicate wire in same cable)---check cable.   
 
 
P7: 
1,PFC board fault.---change PFC board.       
2,Communication of main board and PFC board fault.---check wires of main board and PFC board.   
 
P8: 
1,Less refrigerant.---add refrigerant.   
2,Coil pipe sensor can’t contact with coil pipe.   
3,4-way valve fault.---change 4-way vavle fault. 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

background image

 

61                         SERVICE MANUAL FOR CMV

 

1 3 .   E X P L O D E D   V I E W S   A N D   S P A R E   P A R T S   L I S T S  

13.1 outdoor unit :CMV-50V3A-E2 

 

 

 

 

 

 

NO. description 

name 

number

前网罩 

front grill 

前面板 

front panel 

风叶 

fan 1 

室外电机 

motor 1 

电机支架组件  motor bracket assemble

左护网 

left grill 

左侧立柱 

left pole 

顶盖板 

top cover 

背网 

rear grill 

10 

冷凝器 

condenser 1 

11 

四通阀 

4-way valve 

12 

消音器 

muffle 1 

13 

过滤器 

filter 1 

14 

控制器 

controllor 1 

background image

 

62                         SERVICE MANUAL FOR CMV

 

15 

电控盒盖 

control box cover 

16 

电控盒 

electrical control box 

17 

A机DN8截止阀 

DN8 valve for A unit 

18 

A机DN4截止阀 

DN4 valve for A unit 

19 

B机DN8截止阀 

DN8 valve for B unit 

20 

B机DN4截止阀 

DN4 valve for B unit 

21 

阀座板 

valve installation plate

22 

大抽手 

handle 1 

23 

右侧板 

right panel 

24 

电子膨胀阀 

expand valve 

25 

压缩机 

compressor 1 

26 

压缩机胶垫 

compressor pad 

27 

中隔板 

partition board 

28 

底盘组件 

base assemble 

 

 

 

 

 

 

 

 

 

 

13.2 outdoor unit :CMV-71V3A-T 

 

background image

 

63                         SERVICE MANUAL FOR CMV

 

NO. description 

name 

number

NO.

description name 

number

顶盖 

top cover 

15 

单接头 DN8  sigle tie-in DN8

冷凝器 

condenser 1 

16 

单接头 DN4  sigle tie-in DN4

电机支架 

motor bracket 

17 

单接头 DN10 

sigle tie-in 

DN10 1 

中隔板 

partition board 

18 

电子膨胀阀 

expand valve 

汽液分离器 

gas and liquid 

segregator 1 

19 

右前面板 

right front panel

干燥过滤器 

filter 1 

20 

储液罐 

store pot 

油汽分离头

器 

gas and oil segregator 

21 

压缩机 

compressor 1 

后板 

rear panel 

22 

四通阀 

reverse valve 

电控组件 

electrical control 

assemble 1 

23 

底盘 

base 1 

10 

阀座板 

valve installation plate 

24 

前面板 

front panel 

11 

低压阀 

low pressure valve 

25 

网罩 

grill 1 

12 

维修板 

repair plate 

26 

风叶 

fan 1 

13 

抽手 

handle 2 

27 

电机 

motor 1 

14 

高压阀 

high pressure valve 

   

   

   

   

 

 

 

 

13.2 outdoor unit :CMV-V80WC3AQ 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

background image

 

64                         SERVICE MANUAL FOR CMV

 

 

NO. description 

name 

number

NO.

description name 

number

顶盖 

top cover 

15 

单接头 DN8  sigle tie-in DN8

冷凝器 

condenser 1 

16 

单接头 DN4  sigle tie-in DN4

电机支架 

motor bracket 

17 

单接头 DN10 

sigle tie-in 

DN10 1 

中隔板 

partition board 

18 

电子膨胀阀 

expand valve 

汽液分离器 

gas and liquid 

segregator 

1 19 右前面板 

right front panel

干燥过滤器 

filter 1 

20 

储液罐 

store pot 

油汽分离头

器 

gas and oil segregator 

21 

压缩机 

compressor 1 

后板 

rear panel 

22 

四通阀 

reverse valve 

电控组件 

electrical control 

assemble 

1 23  底盘 

base 1 

10 

阀座板 

valve installation plate 

24 

前面板 

front panel 

11 

低压阀 

low pressure valve 

25 

网罩 

grill 1 

12 

维修板 

repair plate 

26 

风叶 

fan 1 

13 

抽手 

handle 2 

27 

电机 

motor 1 

14 

高压阀 

high pressure valve 

   

   

   

   

 

 

 

13.2 outdoor unit :CMV-V40H13AD 

 

 

 

 

background image

 

65                         SERVICE MANUAL FOR CMV

 

 

NO. description 

name 

number

前网罩 

Front Grill 

面  板 

Front Plate 

轴流风轮 

Axial flow fan 

电  机 

Motor 

电机支架 

Motor support 

冷凝器 

Condenser 

顶盖板 

Top panel 

电器盒 

Electric box  

背网 

Rear Grill 

10 

右侧板 

Right panel 

11 

抽手 

handle 

12 

阀座板 

Valve installation plate 

13 

A 机 DN4 阀 

DN4 valve  

14 

A 机 DN8 阀 

DN8 valve 

15 

B 机 DN4 阀 

DN4 valve  

16 

B 机 DN8 阀 

DN8 valve 

17 

毛细管组件  Capillary Assy 

18 

电子膨胀阀  Electronic expansion valve 

19 

四通阀组件  Four-way valve assembly 

20 

汽液分离器  Steam liquid segregator  

21 

压缩机 

Compressor 

22 

中隔板 

Partition board 

23 

底盘 

Base 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

background image

 

66                         SERVICE MANUAL FOR CMV

 

 

APPENDIX A

 

APPENDIX A 

INSTALLATION AND OPERATION MANUAL 

  I N S T A L L A T I O N   M A N U A L   C M V  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 
 

background image

 

67                         SERVICE MANUAL FOR CMV

 

F o r e w o r d  

This instruction Manual is the universal-purpose version for the models of separate wall-mounted 
air conditioners manufactured by our Co. The appearance of the units that you purchase might be 
s l i g h t l y  d i f f e r e n t  from the ones described in the Manual, but it does not affect your proper 
operations and usage. 

Please read carefully the sections corresponding to the specific model you choose, and keep the 
Manual properly so as to facilitate your reference at later time. 

I M P O R T A N T !  
P l e a s e   R e a d   B e f o r e   S t a r t i n g  

This air conditioning system meets strict safety and operating standards. 
As the installer or service person, it is an important part of your job to install or service the system 
so it operates safely and efficiently. 

For safe installation and trouble-free operation, you must: 
?  Carefully read this instruction booklet before beginning. 

Follow each installation or repair step exactly as shown. 

Observe all local, state, and national electrical codes. 

?  Pay close attention to all danger, warning, and caution notices given in this manual. WARNING: 

This symbol refers to a hazard or unsafe practice which can result in severe personal injury or 
death. 

CAUTION: This symbol refers to a hazard or unsafe practice which can result in personal injury 

and the potential for product or property damage. 

 

 
 

CONTENTS 

LOCATION OF OUTDOOR UNIT 

ELECTRICAL CONNECTION BETWEEN INDOOR AND OUTDOOR UNIT 

INSTALLATION/SERVICE TOOLS (ONLY FOR R410A PRODUCT) 

REFRIGERANT TUBING 

FINAL TASKS 

11 

NOTE: This manual is for Multi split applications only. 

For indoor units installation please refer to the installation manual 
supplied within the indoor unit package. 

background image

 

68                         SERVICE MANUAL FOR CMV

 

1 LOCATION OF OUTDOOR UNIT 

Select the location considering the following: 

O U T D O O R   U N I T  

1 .The location must allow easy servicing and provide good air circulation as shown in fig2. 

2.The unit may be suspended from a wall by a bracked(Optional)or located in a free standing 

position on the floor(preferably slightly elevated). 

3.If the unit is suspended , ensure that the bracket is firmly connected and the wall is strong 

enough to withstand vibrations. 

4.Unit location should not disturb neighbours with noise or exhaust air stream. 

5.Place the mounting pads under the unit legs. 

6.Refer to figure 2 for allowed installation distances. 

.

 

 

background image

 

 

Fig 1 

 

2 ELECTRICAL CONNECTION BETWEEN 

OUTDOOR AND INDOOR UNIT 

ELECTRICAL REQUIREMENTS 
Electrical wiring and connections should be made by qualified electricians and in accordance 
with local electrical codes and regulation.The air conditioner units must be grounded. The air 
conditioner units must be connected to an adequate power outlet from a separate branch 
circuit protected by a time delay circuit breaker,as specified on unit's nameplate. Voltage 
should not vary beyond ± 10% of the rated voltage. 
1 .Remove the power supply cable that is connected to the indoor unit! 
2.To connect the indoor units to the outdoor units,use the following electrical cables. 
Electrical connections: 
Power input cable: 1 group wiresX2.5mm

2

 

cable between indoor and 

outdoor units: 

1 group wiresX 1.0mm

2

 

see Fig 6.7.8.9.10 for detail . 
3.Prepare the cable ends for the power input and for the cables between outdoor and indoor 

units as shown in figure 3a and 3b respectively. 

4.Connect the cable ends to the terminals of the indoor and outdoor units , as show in fig4, figs. 
Please select corresponding connection according to the different indoor units. 5.Secure the 
multiple wire power cable with the cable clamps. 
•Power input cable 

background image

 

70                         SERVICE MANUAL FOR CMV 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

 

 

 

 

 

 

background image

 

71                         SERVICE MANUAL FOR CMV 

3 INSTALLATION/SERVICE TOOLS(QNLY 

FOR R410A PRODUCT) 

C A U T I O N  

New  Refrigerant Air Conditioner Installation 

This air conditioner adopts the new HFC refrigerant (R410A) which does not destroy ozone layer. 

R410A refrigerant is approx . 1.6 times of refigerant R22. Accompanied with the adoption of the 

new refrigerant , the refrigeration machine oil has also been changed. 

Therefore,during installation work, be sure that water , dust , former refrigerant , or refrigeration 

machine oil does not enter into the new type refrigerant R410A air conditioner circuit.The system 

must not be left open to the atmosphere for any reason for any period of time as the systems oil 

quickly absorbs moisture and will contaminate and damage the system. 

A refrigerant liquid line drier is recommended. 

To prevent mixing of refrigerant or refrigerating machine oil ,the sizes of conneting sections of 

charging port on main unit and installation tools are different from those used for the conventional 

refrigerant units. Accordingly,special tools are required for the new refrigerant (R410A) units, 

For connecting pipes use new and clean piping materials with high pressure f i t t i n g  made for 

R410A only, so that water and/or dust does not enter.Moreover, do not use the existing piping 

because there are some problems w i t h  presure f i t t i n g s  and possible i m p u r i t i e s  in e x i s t i n g  

piping . 

Changes in the product and components 

In air conditioners using R410A ,in order to prevent any other refrigerant from being accedentally 

charged .the service port diameter size of the outdoor unit control valve (3 way valve) has been 

changed. (1/2 UFN 20 threads per inch) 

• In order to increase the pressure resisting strength of the refrigerant piping ,flare processing 

diameter and opposing flare nuts sizes have been changed.( fot copper pipes with nomensions 

1/2 and 5/8) 

New tools for R410A 

Nes tools for R410A 

Applicable to R22 model 

Chages 

Gauge manifold 

 

As the working pressure is high ,it is impossible
to measure the working pressure using 
conventional gauges . In order to prevent 
any other refrigerant from being charged , 
the port diameters have been changed. 

Charge hose 

 

In order to increase pessure resisting strength.
hose materials and port sizes have been changed(
to 1 /2 UNF 20 threads per inch). 
When puchasing a charge hose,be sure to confirm
the port size. 

Electronic balance for 
refrigerant charging 

 

 

As working pressure is. high and gasification
speed is fat ,it is difficult to read the indicated
value by means of charging cylinder ,as air 
bubbles occur. 

Torque wrench 
(nominal dia.1/2,5/8) 

 

The size of opposing flare nuts have been 
increased ,incidentally,a common wrench is 
used for nominal diameters 1/4 and 3/8. 

background image

 

72                         SERVICE MANUAL FOR CMV 

Flare tool 
(clutch type) 

 

By incressing the clamp bar'receiving hole 
size , strength of spring in the tool has been
improved. 

Gauge for projection 
adjustment 

 

Used when flare is made by using conventional
flare tool. 

Vacuum pump adapter  0 

 

Connected to conventional vacuum pump,it is 
necessary to use an adapter to prevent vacuum 
pump oil from flowing back into the charge 
hose , 
The charge hose connecting part has two 
ports-one for conventional refrigerant (7/16 
UNF 20 theads per inch )and one for R41 OA ,if 

Gas leakage detector 

 

Exclusive for HFC refrigerant 

 

• I n c i d e n t a l l y , t h e  " r e f r i g e r a n t  cylinder"comes w i t h  the r e f r i g e r a n t  designation(R410A)and 

protector coating in the U.S's ARI specified rose color (Ari color code; PMS 507). 

•Also the "charge port and packing for refrigerant cylinder"requires 1/2 UNF 20 theads per inch 

corresponding to the charge pOse's port size. 

4 REFRIGERANT TUBING 

CONNECT THE INDOOR TO THE OUTDOOR UNIT 

The indoor unit contains a small quantity of nitrogen.Do not unscrew the nuts from the unit until 
you are ready to 

connect the tubing.The outdoor unit is supplied 
with suffcient refrigerant charge(R410A). Refer 
to outdoor unit nameplate. 
To prevent crushing,bend tubes using a bending 
tool. 
NOTE:Use refrigeration R410Atype copper 
tubing only. 
1.Open the valve cover. 
2.Use tubing diameter that corresponds to the 
tubing diameter of the indoor and outdoor units. 
Note that the liquid and suction tubes have 
different diameters.(See tube size,torque 
tightening table.) 
3.Place flares nuts on tube ends before preparing 
them with a flaring tool.Use the flare nuts that 
are mounted on the supplied outdoor and indoor 
units. 
4.Connect the all ends of the tubing to the 
indoor and outdoor units.Notice the sign . All 
ends should correspond one by one. 
5.Insulate each tube separately,and their 
unions,with at least 6mm thick of 
insulation .Wrap the refrigerant tubing,drain 

hose and electric cables together with a vinyl tape (UV protected). 

 

background image

 

73                         SERVICE MANUAL FOR CMV 

Caution! 
When unscrewing the 

valve caps, do not stand 
in front of  them or the 

spindles at any time,as 
the system is under 

pressure. 

Fig 11 
1.INDOOR UNIT 
2.Liquid tube(small dia.) 3.Suction 
tube(large dia.) 4. Plugs 

5.Flare nuts 
6.Tubing between units 7.Suction 

tube 

8.Liquid tube 

9.OUTDOOR UNIT 

10.FIare nuts 

11 .Suction valve(larger) 12.Liquid 
valve(smal) 

NOTE:1.For unit use connectionsA,B and D 

2.For large indoor unit of 5.0KW Use the 

lower connection(unit D) and use the 
3/8"-1/2"transition( supplied) 

3.The electric control channel must match 

the tube channel. 

 

TUBE SIZE 

TORQUE 

Liquid line 1/4" 

1 5 - 2 0  N.M. 

Suction line 3/8" 

3 0 - 3 5  N.M. 

Suction line 1/2" 

5 0 - 5 4  N.M. 

Suction line 5/8" 

7 5 - 7 8  N.M. 

 

 

 

Fig 13 To prevent refrigerant 

leakage,coat the flared 
surface with 
refrigeration oil 

 

Fig 14 

1.Suction valve 
2.Service port 
3.Liquid valve 

EVACUATION OF THE REFRIGERATION TUBES AND THE INDOOR UNIT 

After connecting the unions of the indoor and outdoor units,evacuate the air from the 

tubes and indoor unit as follows: 

Tightening torques 
of unions and 
valve caops: 

background image

 

74                         SERVICE MANUAL FOR CMV

 

1.Connect the charging hoses with a push pin to the low and high sides of the charging 

set and the service ports of the suction and liquid valves. 

Be sure to connect the end of the charging hose with the push pin to the service 

ports. 2.Connect the center hose of the charging set to a vacuum pump. 

3.Open Fully the low and high pressure sides of the manifold gauge valves. 

4.Turn on the vacuum pump.Perform evacuating for at least 30 minutes and than confirm 

that the needle in the gauge moves from 0 MPa(Ocm Hg) t 0 - 0 . 1  MPa(-76cm Hg). 

5.Close the valves of the low and high sides of the charging set and turn off the vacuum 

pump. After few m i n u t e s , i f  the gauge needle has moved,there is a leak which must be 

found and repaired before moving to the next stage. 

6.Disconnect the charging hose from the vacuum pump and from the service ports of the 

suction and liquid valves. 

7.Tighten the service port caps of suction and liquid valves. 

8.Remove the valve caps from all valves,and open them using a hexagonal Allen 

wrench, 9.Securely tighten the caps onto all of the valves. 

10.Check for gas leaks from all the connecting p os i t io n . Tes t  w i t h  electronic  leak 

detector or with a sponge immersed in soapy water for bubbles. 

 

 

 

1 .Charging set 

5.Cap 

9.Liquid valve 

2.Vacuum pump 

6.Suction valve 

10.INDOOR UNIT 

3.OUTDOOR UNIT 

7.Service valve 

1 1.Suction flare connection 

4.Service valve 

8.Cap 

12.Liquid flare connection 

 

 

background image

 

75                         SERVICE MANUAL FOR CMV

 

 

5 FINAL TASKS 

1 .Check all valve caps and ensure that they had tightened properly.Close the valve 

cover. 2.Fill gaps on the wall between hole sides and tubing with sealer. 

3.Attach wiring and tubing to the wall with clamps where necessary. 

4.Operate the unit for no less than 5 minutes at heating or cooling 

mode. 5.Explain filter removal,cleaning and installation. 

6.Operate the air conditioner together with the customer and explain all 

functions. 7.Give the operating and installation manuals to the customer