‘Instope” Ventilation Control 

Symposium

16 October 2002

Lodewyk Roux

Harmony Gold Mining Company Ltd

background image

“Instope Ventilation Control”  Symposium 16/10/2002

“Instope Ventilation Control”  Symposium 16/10/2002

When working hard the human body produces heat at the rate of 
240w/m²

This heat is then removed by - transferred to the ventilating air

For various wet bulb temperatures the actual velocity required will 
vary

I.E.

29.0° Wet Bulb - Velocity = 0.3m/s
30.0° Wet Bulb - Velocity = 0.5m/s
31.0° Wet Bulb - Velocity = 0.9m/s
32.0° Wet Bulb - Velocity = 1.6m/s
32.5° Wet Bulb - Velocity = 2.6m/s 

Î

Max allowable WB Temp

33.0° Wet Bulb - Velocity = 4.0m/s

SLIDE 1

background image

“Instope Ventilation Control”  Symposium 16/10/2002

“Instope Ventilation Control”  Symposium 16/10/2002

Vent Seal

Quantity =20m³/s

Area =10 

Velocity =2.0m/s

SLIDE 6

background image

“Instope Ventilation Control” Symposium 16/10/2002

“Instope Ventilation Control” Symposium 16/10/2002

Ventilation Curtain

Pack not sealed

Packs

Open Area at Packs cannot be ignored

SLIDE 8

background image

“Instope Ventilation Control”  Symposium 16/10/2002

“Instope Ventilation Control”  Symposium 16/10/2002

Ventilation Curtain

Gaps in ventilation curtains

Open Area between ventilation control and hanging cannot be 
ignored

SLIDE 9